Emerson liebert gxt5000r-208 User Manual

Page of 32
 
25
BATTERY CABINET SPECIFICATIONS
GXT5VBATTW120
MODEL NUMBER
GXT5VBATTW120
DIMENSIONS: inches (mm)
Unit: W x D x H
16.1 x 23.6 x 5.1 (410 x 600 x 130)
Shipping: W x D x H
23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit
121.7 (55.2)
Shipping
132.3 (60.0)
AC PARAMETERS – AUXILIARY AC POWER
Nominal AC Input
208 VAC, 50/60 Hz, 400 VA, Single-Phase
Nominal AC Output
120 VAC, 50/60 Hz, 400 VA, 0.75 PF (Power Factor)
Output Receptacles
5-15R (2)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Qty. x Battery Voltage x Battery Rating
20 x 12 VDC x 28 watts per cell (10-minute rate)
Battery Mfg./ Part #
Yuasa 28-12
ENVIRONMENTAL
Operating Temperature
+32°F to +104°F (0°C to +40°C)
Storage Temperature
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
AGENCY
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A 
Transportation
ISTA Procedure 1A
GXT5VBATT
MODEL NUMBER
GXT5VBATT
DIMENSIONS: inches (mm)
Unit: W x D x H
16.1 x 18.5 x 5.1 (410 x 470 x 130)
Shipping: W x D x H
23.2 x 31.1 x 12.8 (590 x 790 x 325)
WEIGHT: lbs (kg)
Unit
107.3 (48.7)
Shipping
116.6 (52.9)
BATTERY PARAMETERS
Type
Valve regulated, nonspillable, lead acid
Qty. x Battery Voltage x Battery Amp Rating
20 x 12 VDC x 28 watts per cell (10-minute rate)
Battery Mfg./ Part #
Yuasa 28-12
ENVIRONMENTAL
Operating Temperature
+32°F to +104°F (0°C to +40°C)
Storage Temperature
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
AGENCY
Safety
UL 1778, c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A 
Transportation
ISTA Procedure 1A