alpha-industries 2000 User Manual
21
3
Operation
Alpha Technologies
3.6
Battery Replacement
The batteries are replaced without shutting off the unit or the loads. Replace them with the same
quantity and type as the originals.
quantity and type as the originals.
DANGER: Make sure you have read the safety instructions in the front of this manual.
Only qualified personnel should change them.
Only qualified personnel should change them.
Procedure
WARNING: Do not replace the batteries when the ON-BATT LED is on.
1
Enable the manual bypass (Section 3.4).
2
Pop off and remove the front cover..
3
Unscrew and remove the battery cover..
4
Remove the battery cartridge from the unit. Take note of the battery configuration and wiring.
5
Replace the batteries with any of the qualified batteries listed in Figure 3.4.
6
Push the cartridge with the new batteries back into the unit.
7
Reinstall the battery cover..
8
Reinstall the front cover..
9
Disable the manual bypass (Section 3.4)
10
Do a self test (Section 3.3).
Battery Replacement Finished
Model
Battery Type
# of Batteries
Manufacturer
Pinnacle Plus 700
12V, 7.2 AH
2
CSB-GP1272
Panasonic LC-R127R2P
Hitachi HV7-12F2
Pinnacle Plus 1000
3
Pinnacle Plus 2000
6
Pinnacle Plus 1500
12V, 9.0 AH
3
CSB HR1234W F2
Pinnacle Plus 3000
6
Figure 3.4
Qualified Replacement Batteries