alpha-industries 2000 User Manual

Page of 30
3
Operation
22
Alpha Technologies
3.7
Specifications
700/700RM
1000/1000RM
1500/1500RM
2000/2000RM
3000/3000RM
Electrical
Output VA (W)
700 (490)
1000 (700)
1500 (1050)
2000 (1400)
3000 (2100)
Input/Output Voltage (VAC)
100 / 110 / 115 / 120 / 127
Input Current (Max); Amps,
120 VAC Units
10
12
15
20
30
Input Frequency (Hz)
50 / 60 (Auto Sensing)
Output Frequency (Hz)
50 / 60 ± 0.5%
Transfer Time (mSec)
0
Crest Factor
3:1
Harmonic Distortion
< 3% of THD at linear load
Output Waveform
Sine
UPS Design Technology
On-Line, fully digitized microprocessor controlled
High Efficiency Mode
(AC to DC)
>95%
Overload Recovery
Auto transfer to UPS
Surge Protection
120V: IEEE C 62.41 / 230V: IEEE 61000-4-5 Level 3
Overload Protection
125% for 1 minute and 150% for 10 seconds
Short Circuit Protection
UPS output automatically cut off or input fuse/circuit breaker protection
Battery Type
Sealed, maintenance free lead acid
Battery Protection
Cut off when battery is low to prevent drainage
Battery Recharge Time
4 hours to 90% of capacity
Communication
RS-232 serial port / USB port / built-in SNMP slot
Mechanical
Tower Dimensions
W x D x H; in (mm)
6.0 x 16.5 x 9.4 (152 x 420 x 238)
8.9 x 16.7 x 14.2 (225 x 425 x 360)
Tower Weight; lb (kg)
29.7 (13.5)
35.6 (16.2)
37.4 (17.0)
68.4 (31.1)
72.6 (33.0)
Rack Mount Dimensions
W x D x H; in (mm)
16.9 x 16.7 x 3.3 (428 x 425 x 84)   (2RU)
16.9 x 25.0 x 3.3 (428 x 635 x 84)
(2RU)
Rack Mount Weight; lb (kg)
32.1 (14.6)
37.6 (17.1)
39.8 (18.1)
69.5 (31.6)
71.5 (32.5)
Input Connectors
NEMA 5-15P
NEMA L5-20P
NEMA L5-30P
Environmental
Operating Temperature °F(°C)
32-104 (0-40)
Storage Temperature °F(°C)
-4-122 (-20-50)
Altitude (Max); ft (m)
15000 (3500)
Audible Noise @1 m
< 40 dBA
Humidity
up to 95%, non-condensing
Conformance
Safety (Designed to Meet)
UL 1778 / CSA
EMC (EMS / EMI)
IEC 61000-4 / FCC Part 15 Class B / CISPR 22