APC mgetm galaxytm 6000 User Manual

Page of 46
6739381EN/
Installation
 (cont.)
Link to an IBM AS/400
® 
computer
Connections:
connections are made to the female
client connectors XR1 and XR2 on the
"Media Contacts 9" relay board;
the corresponding male connectors
are supplied;
see figure 28 for the wiring diagram.
A five-wire cable (not supplied) is
required;
on the AS/400
®
 side, use a 9 or
15-pin SUB-D connector, depending on
the type of AS/400
®
.
Connection of the "LED" remote indications unit
This unit is connected to connectors
XR1 and XR2 of the remote relay
boards of the rectifier-inverter and
Static Switch Cubicles (see the location
of these boards in the figures of the
"connection of power circuits" section).
Connection of "Tele Monitor" remote control and indication unit 
(option)
Connection of "Tele Monitor" remote control and indication unit
Fig. 27
For the installation of the unit and
details of connections at the unit end,
see the instructions delivered with the
unit nr 5102990400.
recommended cable cross-section:
1 mm
2
.
This unit is connected by means of a
signal loop connecting the XR10
connectors of the RAUZ 1 boards of the
rectifier-inverter and Static Switch
Cubicles to the unit connectors. These
RAUZ 1 boards are located near the
remote relay boards.
recommended cable cross-section:
shielded 0.4 mm
2
 cables;
consult manual 6739388XU for
further information.
The MGE
TM 
Galaxy
TM
 6000 UPS can
dialogue with an IBM AS/400
®
computer via this link in compliance
with IBM communication
recommendations, thus enhancing the
protection provided by your
MGE
TM 
Galaxy
TM
 6000 UPS.
The IBM AS/400
®
 computer must be
configured for the link. This document
presents the physical connections
required as well as the system values
that must be modified on the AS/400
®
.
For further information, consult the
following IBM documents:
"Planning Guide, Appendix E"
concerning physical connections;
"Back-up and Recovery Guide",
chapter 7 "Power Loss Recovery"
concerning configuration of the
AS/400
®
.
connector XR10
reception
 –
reception
 +
transmission
 –
transmission
 +
to  connector XR081
on the COMZ board
in the "Tele Monitor" unit
to connector XR10
of another rectifier-inverter
or static switch cubicle
RAUZ 1 board
1
2
3
4
5
6
7
8
9
10
XM097
XM096
1
10
XR11
XR10
XM098
2
4
9
7