hearth-and-home-technolog sl-350trs-ce-d User Manual

Page of 44
Heat & Glo  •  SL-350TRS-CE-D  •  2033-900  Rev. N  •  10/07
30
V
= VENT  TERMINAL
X
= AIR SUPPLY INLET
= AREA WHERE TERMINAL IS NOT PERMITTED
Figure 37 Vent Termination Minimum Clearances
L
= 2.1 M ...................... clearance above paved side-
walk or a paved driveway lo-
cated on public property
M** = 45.8  cm ................. clearance under veranda, porch,
deck, balcony or overhang
106.7 cm ............... vinyl
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
  **
only permitted if veranda, porch, deck or balcony is fully open on
a minimum of 2 sides beneath the floor, or meets Note 2.
NOTE 1: On private property where termination is less than 2.1 M
above a sidewalk, driveway, deck, porch, veranda or balcony, use of
a listed cap shield is suggested. (See vents components page)
NOTE 2: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions specified for
vinyl or non-vinyl siding and soffits. 1. There must be 91.4 cm minimum
between termination caps. 2.  All mechanical air intakes within 3.0 M of
a termination cap must be a minimum of 91.4 cm below the termination
cap. 3. All gravity air intakes within 91.4 cm of a termination cap must
be a minimum of 30.5 cm below the termination cap.
M
N
P
R
Q
(See Note 2)
Electrical
Service
V
S
V
S
V
T
D*
V
NOTE 3: Local codes or regulations may require different
clearances.
NOTE 4: Termination caps may be hot. Consider their proximity to
doors or other traffic areas.
NOTE 5: Location of the vent termination must not interfere with
access to the electrical service.
NOTE: Vent system termination is permitted in porch areas with
two or more sides open. You must follow all side walls, over-
hang and ground clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper perfor-
mance of the appliance when the venting system does not meet
these requirements.
D
E
B
L
v
v
v
v
v
v
v
v
B
B
A
H
M
X
J or K
I
A
G
F
.91M
B
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
______________________________________________________________________
    
Q
MIN
     R
MAX
  1 cap
  
91.4 cm
   2 x Q 
ACTUAL
  2 caps
  1.8 M
   1 x Q 
ACTUAL
  3 caps
  2.7 M
2/3 x Q 
ACTUAL
  4 caps
3.7 M
1/2 x Q 
ACTUAL
Q
MIN
 = # termination caps x 3        R
MAX
 = (2 / # termination caps) x Q
ACTUAL
N
= 15.3  cm ................. non-vinyl sidewalls
30.5 cm ................. vinyl sidewalls
P
= 2.4 M
S =  15.3 cm .................. clearance from sides of
electrical service
T = 30.5  cm ................... clearance above electrical
service
(See Note 5)
(See Note 5)
A
= 30.5 cm ............... clearances above grade, veran-
da, porch, deck or balcony
B
= 30.5  cm ............... clearances to window or door
that may be opened, or to per-
manently closed window.
(Glass)
D*
= 45.8  cm ............... vertical clearance to unventilat-
ed soffit or to ventilated soffit lo-
cated above the terminal
    *76.2 cm ............... for vinyl clad soffits and below
electrical service
F
=  22.9 cm .............. clearance to outside corner
G
= 15.3 cm ............... clearance to inside corner
H
= 91.4 cm ............... not to be installed above a gas
meter/regulator assembly within
91.4 cm horizontally from the cen-
ter-line of the regulator
I
= 91.4  cm ............... clearance to gas service regu-
lator vent outlet
J
= 22.9 cm ................. clearance to non-mechanical air
supply inlet to building or the
combustion air inlet to any other
appliance
K
= 91.4 cm ................. clearance to a mechanical (pow-
ered) air supply inlet
(See Note 1)
(See Note 1)
Alcove Applications