84/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
9.4 
CONNECTION FOR OPTIONS 
 
The installation and cabling of the options must be performed a qualified 
service person. 
 
9.4.1  Remote Signaling Box (RSB) 
The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential 
free contacts fitted on the P4 - Customer Interface Board of the UPS. 
It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be 
surface mounted. 
The remote panel contains an internal buzzer and the following status indicators: 
• 
Mimic diagram with 
LED's indicating the operation of Rectifier and Inverter, and the power 
source supplying the critical Load
• 
Alarm 
(LED light and audible alarm) indicating a critical situation on the UPS. 
• 
Stop 
indicating the UPS is preparing to shut down in a short time. 
• 
Mute 
push button to reset the buzzer. 
• 
Test 
push button checks all the LED’s and the buzzer of the remote panel. 
 
The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm
2
.
 
The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included). 
Maximal admitted length: 985 ft (300 m). 
It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board). 
 
 
The alarms on free potential contacts can be connected on terminals X1 
instead J2
 (see correlation X1 – J2 in chapter 8.1). 
 
Mute
Test
max 985ft / 
300m
yellow/brown
white/yellow
1
2
4
3
5
brown/green
7
6
8
10
9
11
white/green
blue/red
violet
grey/pink
13
12
14
16
15
17
yellow
green
brown
20
22
23
19
18
21 white
24
16
COMMON ALLARM
AUX. BUZZER
STOP OPERATION
20
22
23
17
19
38
LOAD ON MAINS
LOAD ON INVERTER
56
55
50
43
44
49
40
42
SIGNALLING
UTILITY FAILURE
GND
24V
34
37
33
32
31
X15
IM6544
1
2
J2
 -
 SU
B D - MA
LE
REMOTE
X3
X4
A
A
B -
P4 - IM0005
B
PLUG
J2
77
m
m
in
130
mm
216mm
5 1/
4"
 in
8 1/2" in
25
black
P.S.: The above mentioned colors are
XA
TERMINALS BLOCK
TERMINALS
XA
pin
k
red
bl
ue
gre
y
pink
red
grey
blue
SUB D - MALE
suitables only for XY standard cable
S
G
T
50
0
0_
O
P
T
_
01
0
-1
5
0_
R
M
S
_0
1U
S
1
12
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
1
14
9
1
2
1
1
2
3
4
1
2
3
4
J2
XA
BLOCK
BOX
Pink + Red
Grey + Blue
Stop
Alarm
g
GE Digital Energy
Customer Interface
2
1
 
Fig. 8.4.1-1   Remote Signaling Box connection
 
 
 
A Terminals 
X3X4 and X15 fitted inside the Remote Signaling Box
 
Plug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female-
25 pin) located on P4 - Customer Interface Board
 
XA Terminals 
block 
XA for 24 VDC / 1A supply Remote Signaling Box
 
 
If the remote signal panel is plugged on connector J2, the terminal blocks X1 
cannot be used to drive an external alarms monitoring device, because it is 
supplied by the internal UPS low voltage power supply.