heatcraft-refrigeration-p h-im-fl1a User Manual

Page of 24
4
Figure 2. Solid Mount for Mobile or Deep
 
 Sump Application.
Condensing Unit Rigging and Mounting 
 
Rigging holes are provided on all units. Caution should be 
exercised when moving these units. To prevent damage to the 
unit housing during rigging, cables or chains used must be held 
apart by spacer bars. The mounting platform or base should be 
level and located so as to permit free access of supply air. 
Ground Mounting
Concrete slab raised six inches above ground level provides a 
suitable base. Raising the base above ground level provides 
some protection from ground water and wind blown matter. 
Before tightening mounting bolts, recheck level of unit. The unit 
should in all cases be located with a clear space in all directions 
that is at a minimum, equal to the height of the unit above 
the mounting surface. A condensing unit mounted in a corner 
formed by two walls, may result in discharge air recirculation 
with resulting loss of capacity.
Roof Mounting 
 
Due to the weight of the units, a structural analysis by a 
qualified engineer may be required before mounting. Roof 
mounted units should be installed level on steel channels or 
an I-beam frame capable of supporting the weight of the unit. 
Vibration absorbing pads or springs should be installed between 
the condensing unit legs or frame and the roof mounting 
assembly. 
 
Access 
 
Provide adequate space at the compressor end of the unit for 
servicing. Provide adequate space on the connection side to 
permit service of components. 
Spring Mounted Compressor 
 
Compressors are secured rigidly to make sure there is no transit 
damage. Before operating the unit, it is necessary to follow 
these steps: 
a. 
Remove the upper nuts and washers.
b. 
Discard the shipping spacers.
c. 
Install the neoprene spacers. (Spacers located  
 
in the electrical panel or tied to compressor.)
d. 
Replace the upper mounting nuts and washers.
e. 
Allow 1/16 inch space between the mounting nut/ 
 
washer and the neoprene spacer.
Rigid Mounted Compressor 
 
Some products use rigid mounted compressors. Check the 
compressor mounting bolts to insure they have not vibrated 
loose during shipment.
 Ambient Fan Cycle Control
This is an automatic winter control method which will maintain 
a condensing pressure within reasonable limits by cycling 
fan motors in response to outside air temperature. The 
thermostat(s) should be field adjusted to shut off the fan when 
the condensing temperature is reduced to approximately 90
˚
F. 
Table 2 on page 5 lists approximate settings for several system 
T.D.ʼs. These settings are approximate as they do not take into 
account variations in load.
CAUTION:  Under no circumstance should all    
 
condenser motors be allowed to cycle  
 
off on one control. At least one motor  
 
shall be wired to operate at all times.  
 
Under most circumstances, the  
 
 
condenser motor nearest the inlet    
 
header should remain on whenever the  
 
compressor is operating.