Features 
(continued)
 
Health Monitoring 
Operation 
 
• 
Control Signals – 0/4 to 20 mA,  
0/1 to 5 Vdc, 0 to 10 Vdc, Digital 
remote setpoint (RS485 Modbus 
RTU protocol). 
• 
Output Signals – 0/4 to 20 mA,  
0/1 to 5 Vdc and slidewire 
emulation. 
• 
Manual Operation – All 11280S 
series actuators are supplied with a 
manual handwheel to operate the 
actuator when power is not 
available. 
• 
Auto-Manual – electric handswitch 
with auxiliary contacts indicating an 
"Out-of-Auto" position is available 
for local electric control. 
• 
RS485/Modbus RTU 
Communication
 – Simple and 
easy to use Modbus RTU 
communication is standard with all 
11280S actuators allowing 
seamless networking of Honeywell 
control products.  
• 
Auxiliary Outputs – Two types of 
auxiliary outputs can be specified, 
SPDT switches or 
electromechanical relay outputs.  
Relay outputs can be programmed 
to output alarm conditions, provide 
control of other equipment, or 
indicate status.  
• 
Alarm Functions – Alarms may be 
assigned to relay outputs or may be 
accessed through Modbus.  Alarms 
can be triggered from stall, 
temperature limits, motor cycle 
count, out of automatic mode, 
digital input, position, input failure, 
position sensor failure, power up 
failure, and more. 
• 
Local HMI Configuration – An 
integral keypad and high intensity 
display is available for non-intrusive 
local configuration of the actuator 
(Figure 2). 
• 
Configuration Security – 
Password protection is provided, 
allowing users to lock out some, all, 
or no groups of setup parameters to 
prevent tampering. 
 
 
 
• 
Factory Calibration – Factory 
calibration is stored in non-volatile 
memory and can be restored via 
the local HMI at any time. 
• 
Direction of Rotation – Direction 
of rotation on increasing input 
signal is programmable. 
• 
Split Range Operation – Split 
range is programmable and 
infinitely adjustable. 
• 
Digital Input Override – A digital 
input is provided and is 
programmable to provide override 
of all other input signals as an 
emergency override of control. The 
digital input can be programmed to 
drive the actuator open, closed, 
remain in-place, or to a user-
specified position on contact 
closure. 
• 
Failsafe – When input signal 
exceeds high or low range limits 
(or input signal failure), the 
actuator can be programmed to 
drive open, closed, remain in-
place, or drive to a user-specified 
position. 
Construction 
 
• 
Enclosure – Rugged, industrial 
grade enclosure. 
• 
Low Maintenance – Simple-
proven design means high 
reliability/low maintenance. 
• 
Output Shaft Hardware – All 
11280S series actuators are 
supplied with an adjustable radius 
crank arm. Optional linkage kits 
are available. 
• 
Limit Switches – Two end-of-
travel electric limit switches are 
supplied as standard equipment 
with all 11280S series actuators. 
• 
Warranty – Exceptional warranty. 
 
A standard feature on all 11280S 
actuators accumulates information 
about actuator operation.  This 
information then can be used to 
evaluate and determine predicted or 
scheduled maintenance periods.  The 
parameters that are monitored include: 
accumulated stall time, thermal 
operating rating of the actuator 
exceeded, number of motor starts in a 
region of motor travel, total travel and 
current actuator travel.
 
 
Non-Contact 
Position Sensing 
Honeywell 11280S series actuators 
implement a variable inductance, non-
contact position sensor mounted directly 
to the actuator output shaft providing 
precision position sensing from 0 to 90 
degrees, (Figure 3).  This technology 
eliminates maintenance items such as 
wipers, bearings, as well as static 
friction, hysteresis and electrical noise 
over a wide range of demanding 
environmental conditions. 
 
Slidewire Emulation
 
The Slidewire Emulation Circuit (SEC) 
emulates the proportional voltage 
output of a typical slidewire through a 
high impedance circuit.  The voltage 
output is proportional to the supply 
voltage and shaft position.  A non-
contact position sensor is used to 
determine shaft position in place of the 
slidewire.