Honeywell 11280s User Manual

Page of 14
61-86-03-13 
Page 4 
 
Set Up/Configuration Parameters 
 
Configuration parameters are logically grouped and accessed using the local HMI.  Actuator calibration is also 
accomplished through a simple procedure using the keypad.  By pressing the SETUP button on the HMI, you can step 
through the set up groups that contain all of the configuration parameters.  The table below summarizes the configuration 
parameters available within the various set up groups. Full details of all configuration parameters are found in the 11280S 
Series Smart Actuator Installation, Operation and Maintenance Manual
, document number 61-86-25-09. 
 
  
Set Up Group 
Configuration Parameter Selections/Settings 
SET INPUT
 Selects various 
parameters that define actuator 
operation. 
 
IN TYP – Input Actuation Type 
INP HI – Input High Range Value 
INP LO – Input Low Range Value 
FILTYP – Input Filter Type 
LPFILT – Low Pass Filter Time Constant 
Direct – Actuator Rotation 
Dband – Input Deadband  
FsTYP – Failsafe Type 
FsVAL – Failsafe Value 
CHAR – Input Characterization 
LDCAL – Restore Calibration Type 
 
SET RELAY
 When the actuator 
is equipped with optional relays, 
this set up group allows you to set 
relay action for various actuator 
operating conditions.  Contact 
closure can be wired to external 
annunciators or alarm points to 
indicate conditions for any of the 
Relay Types.  
RTYPnn – Relay Type 
Input Range 
Position Range 
Deviation 
Upper or Lower Limit Travel  
Temperature High or Low  
Motor Starts 
Motor Stalled 
Manual Mode 
Power Up Test Failure 
Input Signal Failure 
Position Sensor Signal Failure 
Digital Input Closure 
RnnE – Relay Count Multiplier 
RnnVAL – Relay Value 
Rnn HL – Relay High/Low 
RLYnHY – Relay Hysteresis 
SET CUROUT
 Selects the 
current (or voltage) output range 
of the actuator. 
CUROUT - Output Signal Range 
4 – 20 mA, 
0 – 20 mA, 
1 – 5V, 
0 – 5V, 
SW  E (Slidewire Emulation) 
 
SET COMM
 Actuator can be 
defined as a master or slave 
device on a Modbus RTU RS-485 
loop.  Operating setpoint can be 
transmitted to the actuator and 
operating status can be read 
when connected to supervisory 
control systems. 
COMM – Communications Parameters 
ADDRES – Device Address 
BAUD – Baud Rate 
XmtDLY – Response Delay 
DBLBYT – Floating Point Data Format 
 
SET DIGINP
 
Selects digital 
input action upon contact closure
. 
DIGINP – Digital Input State 
Endpos – End Position Value 
 
SET DISPLA
 Selects desired 
decimal places and engineering 
units for local display. 
DECMAL – Decimal Point Location 
EUNITS – Units Display 
UNITS – Display Units 
 
CAL  INPUT, MTR, CURENT
 If needed, calibration of the actuator input, motor position and actuator output can be 
performed using the local keypad and display. 
 
 
Continued on next page