ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR
63-2505
4
Environmental Protection Ratings: NEMA1 standard with 
damper shaft in horizontal position.
Accessories:
205617 Hub Insert, 3/4 in. round.
205753 Hub Insert, 3/8 in.
205758 Hub Insert, 5/8 in.
205820A 3-Point Mounting Kit.
205685 Crank-Arm Accessory.
205850B End Stop Kit.
INSTALLATION
When Installing this Product…
1. Read instructions carefully. Failure to follow them could 
damage the product or cause a hazardous condition.
2. Check ratings and description given in the specifications 
to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power before installation to prevent 
electrical shock or equipment damage.
CAUTION
Equipment Damage Hazard.
Can cause equipment damage or failure.
1. Never turn motor output hub by hand or wrench.
2. Do not install actuator in areas with acid fumes or 
other deteriorating vapors that might attack the 
metal parts of the actuator. 
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.
Do not install actuator in areas with escaping gas or 
other explosive vapors that could be ignited by a spark 
from the actuator or attached accessories.
Location
Install the actuator in any location free from acid fumes or 
other deteriorating vapors that might attack the metal parts of 
the actuator. Make sure the location is not subject to escaping 
gas or other explosive vapors that could accidentally be 
ignited by a spark from the actuator or its attached parts.
Install the actuator in a location that allows enough clearance 
for mounting accessories and for servicing.
Mounting
The ML6284 Non-Spring Return Direct Coupled Damper 
Actuator is designed to operate a damper by driving the 
damper shaft either cw 
 or ccw
 depending on 
damper design. All actuators are shipped in the fully closed 
position.
The ML6284 Non-Spring Return Direct Coupled Damper 
Actuator is designed with removable hub inserts to 
accommodate specific damper shaft sizes. Proper sleeve 
selection is necessary when three-point mounting is used to 
avoid excessive strain on the output gear. Most ML6284 
Actuators are shipped with a 1/2 in. hub insert. For field use, 
two hub insert sizes are available. See the Accessories listing 
in the Specifications section. Shaft sizes are stamped on the 
inserts.
The ML6284 Non-Spring Return Direct Coupled Damper 
Actuator is designed for single-point mounting when using a 
mounting bracket. Single-point mounting is typically used 
when the actuator is mounted on the damper shaft.
The ML6284 Non-Spring Return Direct Coupled Damper 
Actuator can be mounted directly on the damper shaft with the 
actuator in any position.
A mounting bracket (see Fig. 1) is provided with some models 
to aid in installing the actuator. The bracket can be bent to any 
shape to allow the bracket tab to be centered in the actuator 
slot.
CAUTION
Equipment Damage Hazard.
Improper mounting can damage the equipment or 
interfere with proper operation.
The mounting bracket must not bind or clamp the 
actuator to the duct. The mounting bracket only 
prevents the actuator housing from rotating.
The ML6284 Direct Coupled Damper Actuator has a 
reversible output hub. The hub is factory mounted on the top 
of the actuator gear housing. When attaching to damper 
shafts less than 2.5 in. (64 mm) long, or for ease of mounting, 
the output hub may be mounted to the back of the actuator 
gear housing. See Fig. 3. Be careful when removing the 
retaining ring which secures the output hub sleeve to the 
actuator housing. Use a flat headed screwdriver to pry the 
retaining ring loose.