ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR
5
63-2505
Fig. 2. Installing mounting bracket on ML6284 Non-Spring 
Return Direct Coupled Damper Actuator. NOTE: Install 
mounting bracket so mounting bracket tab is centered in 
actuator slot.
A typical actuator mechanical connection is shown in Fig. 4; 
wiring diagrams in Fig. 5 through 10.
The ML6284 Non-Spring Return Direct Coupled Damper 
Actuator can also be three-point mounted using the two front 
gear housing slots and the adapter bracket. Two screws are 
secured through the two front gear housing slots and the 
adapter bracket positioned to secure the rear of the actuator. 
Three point mounting is used for foot mounting the actuator or 
internally mounting the actuator in the duct when direct shaft 
coupling is not possible.
CAUTION
Equipment Damage Hazard.
Improper mounting will damage the actuator.
Do not use the actuator as a shaft bearing. The 
actuator must be used only to supply rotational torque. 
To prevent damage to the actuator, avoid any side 
loads to the actuator output coupling bearings.
Preparation
Before installing the ML6284 on the damper shaft, determine 
the opening direction of the damper shaft (see Fig. 2) to 
correctly connect the wiring. 
Installation
Installing Actuator and Mounting Bracket 
(Single Point Mounting)
1. Place the ML6284 Non-Spring Return Direct Coupled 
Damper Actuator over the damper shaft.
2. Position the actuator for best access to the actuator 
damper shaft locking screw.
3. Install the mounting bracket (see Fig. 2) and adjust it so 
the bracket tab is midway in the actuator slot. Mark the 
screw holes for installing the mounting bracket on the 
damper housing.
4. Remove the mounting bracket and actuator.
5. Drill or center punch the starting holes for the mounting 
bracket screws (or use no.10 self-tapping sheet metal 
screws—not  supplied).
6. Place the actuator and mounting bracket back into 
position over the damper shaft and install the mounting 
bracket screws.
7. Move damper shaft either fully clockwise 
or fully 
counterclockwise
8. Fully depress and hold disengage button while moving 
the actuator hub either fully clockwise
or fully 
counterclockwise
to match the damper shaft. 
Release disengage button.
9. Tighten the two 8 mm by 12 mm long set screws firmly 
against the damper shaft (maximum tightening torque is 
100 lb-in.).
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before wiring to prevent 
electrical shock or equipment damage.
All wiring must comply with local electrical codes, ordinances 
and regulations. The ML6284 is designed for use with a Class 
2 power supply. Voltage and frequency of the transformer 
used must correspond with the characteristics of the motor 
and those of the power supply. Standard electrical connection 
is shown in Fig. 4. See Fig. 5 and 6 for typical wiring 
connections.
The ML6284 has a plastic housing with two taped holes  on 
the end of the device for 1/2 in. conduit fittings.
ML6284 Models with Factory-mounted Auxiliary Switches 
(See Fig. 7)
ML6284C,F models have two nonadjustable low voltage rated 
spdt auxiliary switches that are factory set to make common to 
normally open at 12° and 82° rotation from the closed  
counter-clockwise stop. See Fig. 7.
M7876
ACTUATOR 
SLOT