The over-limit and low-limit temperatures are used in conjunction
with the on-board indicator lights and/or remote alarms to indicate
a fault situation. If the over-limit temperature is reached, power to
all elements will be shut off.
To set temperatures:
1.Press the Scroll button one or more times until the desired function setting LED is lit.
The LCD display now indicates the current function setting.
2.Use the 
L and M buttons to set the temperature higher or lower than the current setting.
See the following section, 
Operating Temperatures, for a list of acceptable temperatures.
3.Press the Scroll button one or more times to either highlight another function or until all func-
tion lights are out, which returns the control unit to operating mode.
MAXIMUM OPERATING TEMPERATURES
Metal Tanks
Maintenance Temperature:
up to 160°F/70°C
Over Limit Temperature:
up to 170°F/75°C
Low Limit Temperature:
up to 155°F/65°C
Crosslinked Polyethylene Tanks
Maintenance Temperature:
up to 130°F/55°C
Over Limit Temperature:
up to 140°F/60°C
Low Limit Temperature:
up to 125°F/50°C
When programming the con-
trol unit is complete,  ensure
that all function lights are
out. When the system is in
programming mode (when one of the
function lights is lit) the heating ele-
ments will still operate but there is a
possibility that the programming may
be changed inadvertently.
Do not exceed
the temperatures
noted at left.
Temperature set-
tings above those listed may result in
damage to the Thermolar system, the
tank and/or the tank contents.
Ensure that the
temperature of
the contents
being loaded into
a tank does not exceed the maximum
temperature setting as noted at left.
Note
The control unit will normally be preprogrammed with the temperatures specified
when the system was ordered. Before operating the system, confirm the temperature
programming.
Note
Set the over-limit temperature at least 10°F/5°C higher than the maintenance 
temperature.