Riello DLD 600 UM6K600735RUB User Manual

Product codes
UM6K600735RUB
Page of 4
27
Dialog Dual 
 3,3-1
0 kV
A
BB 108-7 - BC 108-14
BB 192-7
BC 192-12
BB 240-A3
BC 240-A5
BC 108-38
dld 330-400
dld 500-600
dld 650tm-800-800tm-1000-1000tm
dld 330-400 tower
DLD 650 TM
DLD 800 TM
DLD 1000 TM
6500VA/5200w
8000VA/6400w
10000VA/8000w
4u
19’’
455
175
520
520
4u
19’’
455
175
660
660
630
215
655
4U = 176 mm; 19” = 438 mm
 MODELS
 PowEr
 INPUT
 rated voltage
400 Vac three-phase + N
 minimum voltage (Ph + N)
164 Vac @ load 100% / 84 Vac @ load 50%
 rated frequency
50/60 hz ± 5 hz
 Power factor
> 0.95
 BY PASS
 Voltage range
180 - 264 Vac (selectable in Economy mode and smart mode)
 Frequency range
selected frequency ±5% (user configurable)
 OUTPUT
 rated voltage
220-230-240 Vac selectable
 Voltage distortion
< 3% with linear load / < 6% with non-linear load
 Frequency
50/60 hz selectable
 static variation
1.5%
 dynamic variation
≤ 5% in 20 ms
 waveform
sinewave
 crest factor
3: 1
 BATTERIES
 recharge time
4-6 h
 OVERLOAD CAPACITY
 100% < load < 110%
1’
 110% ≤ load < 150%
4”
 load > 150%
0.5”
 ENVIRONMENTAL
 weight (kg)
64
80
85
 dimensions (hwd) (mm)
2 x 455 x 175 x 660 tower / 2 x 175(4u) x 483 x 660 rack
 Efficiency smart mode
up to 98%
 Protection
overload - short-circuit - overvoltage - undervoltage - temperature - low battery
 communication
usB / rs232 + communication interface slot
 compliance
EN 62040-1 Emc EN 62040-2 directives 2006/95/Ec - 2004/108 Ec EN 62040-3
 operating temperature
0°c ÷ +40°c
 relative humidity
< 95% non condensing
 colour
dark grey rAl 7016
 Noise
< 45 dBA at 1 m
 Accessories provided
2 cable guides; terminal board connection; software; serial cable; plastic keys to release display; handles kit
BATT. BOX MODELS
dld modEl
dimensions (mm)
h
 x 
w
 x 
d