4-1-3-7. 
 Popup menu “Maint. ON”
Indoor units, digital point, and analog point issue alarms. Alarms can be temporarily 
suspended for mechanical work or device malfunctions. When you Register, alarm 
will not be issued when an error occurs. When you Cancel, the alarm function is 
restored. Start/stop control and alarm display are disabled for devices registered for 
maintenance.
Click on the Maint. ON in the popup menu, then click on the Cancel or Register in the 
sub-menu to specify Cancel or Register.
4-1-3-8. 
 Popup menu “Name registration”
Use this menu to change names for any unit. 
When the Password screen is displayed by 
clicking the menu, enter (Password level 
2). When the “Name registration” screen is 
displayed, change the name.
After changing the name, click on the 
 button to change the name and 
close the screen.
Click on the 
 button to close the 
screen without changing the name.
4-1-3-9. 
 Popup menu “Meter value settings”
Use this menu to change the meter value in 
the accumulated value. When the password 
screen is displayed by clicking the menu, 
enter (Password level 2).
When the “Meter value settings” screen is 
displayed, change the Meter pulse count.
After changing, click on the 
 
button to change the data.
Click on the 
 button to restore 
the data before the change. 
Click on the 
 button to close the 
“Meter value settings” screen.
4-1-3-10. 
 Popup menu “High/low-limit alarm settings”
Use this menu to change the high/low-limit alarm 
value of the analog input. When the password 
screen is displayed by clicking the menu, enter 
(Password level 2).
When the “High/low-limit alarm settings” screen is 
displayed, change the high-limit alarm value or low-
limit alarm value.
After changing, click on the 
 button to 
change the data and close the screen.
Click on the 
 button to close the screen without changing the data.