Puls YRM2.DIODE Redundancy Module Specification Guide
YRM2.DIODE
Y-Series
DC24-48V,
20A,
D
UAL
R
EDUNDANCY
M
ODULE
20.6. E
XAMPLE
:
R
EDUNDANCY FOR
C
ONTROLS
The example shows a cost effective solution to get redundant power for a PLC or controller system.
In many cases, two power supplies are used; one for the demanding loads and another one for the controls and
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls.
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls.
Traditional approach:
Load
PS1
PLC
PS2
Improved approach:
Load
PLC
PS1
PS2
YR2
Fig. 20-4 Wiring diagram, redundancy for sensitive loads
Failure
Monitor
Sensitive
Load
e.g.
Controller
optional
I
I
I
L1
L2
L2
PE
L3
I
N
Heavy
Loads
e.g. Motors
L N PE
5A
Power
Supply
+ +
- -
24V, 5A
L1 L2 L3 PE
20A
Power Supply
+ +
- -
24V, 20A
YRM2.DIODE
+
-
OUT
+
-
IN 1
+
-
IN 2 IN 1 IN 2
Note: Use separate mains systems for each power supply whenever it is possible
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
16/18