20.6.  E
XAMPLE
:
 
R
EDUNDANCY FOR 
C
ONTROLS
 
The example shows a cost effective solution to get redundant power for a PLC or controller system.  
In many cases, two power supplies are used; one for the demanding loads and another one for the controls and 
sensitive loads. The power supply for the demanding loads can be used as a redundant source to supply the controls. 
Traditional approach: 
Load
PS1
 PLC
PS2
 
Improved approach: 
Load
PLC
PS1
PS2
YR2
 
 
 
Fig. 20-4   Wiring diagram, redundancy for sensitive loads 
 
Failure
Monitor
Sensitive
Load
e.g.
Controller
optional
I
I
I
L1
L2
PE
L3
I
N
Heavy
Loads
e.g. Motors
L   N  PE
5A
Power
Supply
+   +
-  -
24V, 5A
L1  L2  L3 PE
20A
Power Supply
+   +
-  -
24V, 20A
YRM2.DIODE
+  
-
OUT
 -
IN 1
+  
-
IN 2 IN 1 IN 2
 
Note: Use separate mains systems for each power supply whenever it is possible
 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 