Puls ML50.100 Power Supply Specification Guide
ML50.100, ML50.109
MiniLine
24V, 2.1A, S
INGLE
P
HASE
I
NPUT
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/20
14. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 14-1 Front side
DC-OK LED (green)
On when the voltage at the
output terminals is > 20 V
output terminals is > 20 V
DC-OK LED and DC-OK signal
functions are synchronized
functions are synchronized
Output Voltage
Potentiometer
Turn to set the output voltage.
Factory set: 24.5V
Potentiometer
Turn to set the output voltage.
Factory set: 24.5V
Input Terminals
Spring-clamp terminals
N … Neutral input
L … Line (hot) input
Spring-clamp terminals
N … Neutral input
L … Line (hot) input
... PE (Protective Earth) input
Output & Signal Terminals
Spring-clamp terminals
Dual terminals per pole
Spring-clamp terminals
Dual terminals per pole
+ Positive output
- Negative (return) output
Dual pins per pole
DC-OK Open collector output
Indicates an output
voltage higher than
20Vdc
- Negative (return) output
Dual pins per pole
DC-OK Open collector output
Indicates an output
voltage higher than
20Vdc
15. T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring. Mounting and wiring do not require any screwdriver.
other (input below, output above) to help in error-free wiring. Mounting and wiring do not require any screwdriver.
Type
Quick-connect
spring-clamp
terminals
Solid
wire
0.3-4mm
2
Stranded
wire
0.3-2.5mm
2
American wire gauge
26-12 AWG
Ferrules
Allowed, but not required
Wire stripping length
6mm / 0.25inch
Pull-out force
12AWG:60N, 14AWG:50N, 16AWG:40N
(according to UL486E)
(according to UL486E)
Fig. 15-1 Connecting a wire
Instructions:
a)
Use appropriate copper cables
b)
Follow local and national installation codes and
regulations!
regulations!
c)
Ensure that all strands of a stranded wire enter
the terminal connection!