Puls ML50.100 Power Supply Specification Guide
ML50.100, ML50.109
MiniLine
24V, 2.1A, S
INGLE
P
HASE
I
NPUT
Mar. 2007 / Rev. 1.0 DS-ML50.100-EN
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/20
17. E
NVIRONMENT
Operational temperature
-10°C to +70°C (14°F to 158°F)
Reduce output power according to
Fig. 17-1
Output de-rating
1.3W/°C
60-70°C (140°F to 158°F), see
Fig. 17-1
Storage temperature
-40 to +85°C (-40°F to 185°F)
Storage and transportation
Humidity
5 to 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
2 hours / axis
IEC 60068-2-6
Shock
20g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude
0 to 6000m (0 to 20000ft)
Reduce output power or ambient
temperature above 2000m sea level.
temperature above 2000m sea level.
Output de-rating (for altitude)
3W/1000m or 5°C/1000m
Above 2000m (6500ft), see
Fig. 17-2
Over-voltage category
III
EN 50178, IEC 62103 altitudes < 2000m
II
Altitudes from 2000m to 6000m
Degree of pollution
2
EN 50178, IEC 62103, non conductive
Fig. 17-1 Output current vs. ambient temp.
Fig. 17-2 Output current vs. altitude, 24V
0
-10
0
20
40
70°C
0.4
0.8
1.2
1.6
2.0
2.4A
60
Ambient Temperature
Allowable Output
Current at 24V
Current at 24V
0
0
2000
4000
6000m
0.4
0.8
1.2
1.6
2.0
2.4A
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
C... Tamb < 40°C
A
B
C
Allowable Output
Current at 24V
Current at 24V
The ambient temperature is defined 2cm below the unit.
18. P
ROTECTION
F
EATURES
Output
protection
Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
typ. 36V
max. 39V
max. 39V
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Output over-current protection electronically
limited see
Fig. 10-1
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 2.5mm in diameter
E.g. screws, small parts
Over-temperature protection
not included
Input transient protection
MOV
Metal Oxide Varistor
Internal
input
fuse
T3.15A H.B.C.
Not user replaceable
Note: In case of a over-voltage, overload, no-load or short-circuit event, an audible noise may be heard.