Puls QS10.241 Power Supply Specification Guide
![Puls](https://files.manualsbrain.com/attachments/f7041454b866cfdaa2ab969e2fceed93f951f2f9/common/fit/150/50/2534d33282a162a3c2687862aa5026f5d26de2af0500a4f43b3b09ee366e/brand_logo.gif)
QS10.241, QS10.241-A1/ -C1/ -D1
Q-Series
24V,
10A,
S
INGLE
P
HASE
I
NPUT
4. DC-I
NPUT
QS10.241, QS10.241-A1, QS10.241-C1:
DC input
nom.
DC 110-150V
-20%/+25%
DC input range
min.
88-187Vdc
continuous operation
DC input current
typ.
2.37A
110Vdc, at 24V, 10A
QS10.241-D1:
DC input
nom.
DC 110-300V
-20%/+25%
DC input range
min.
88-375Vdc
continuous operation
DC input current
typ.
2.37/ 0.85A
110/300Vdc, at 24V, 10A
All units:
Allowed Voltage L/N to Earth
max.
375Vdc
continuous, IEC 62103
Turn-on voltage
typ.
80Vdc
steady state value
Shut-down voltage
typ.
55Vdc
steady state value
Fig. 4-1 Wiring for DC Input
Instructions for DC use:
+
-
Load
L
PE
+
-
Power Supply
AC
Battery
N
DC
a) Use a battery or similar DC source.
For other sources contact PULS
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to a earth wire or to the machine
c) Connect the PE terminal to a earth wire or to the machine
ground.
d) A supply from the intermediate DC-bus of a frequency
converter is not recommended and can cause a
malfunction or damage the unit.
malfunction or damage the unit.
Nov. 2011 / Rev. 2.1 DS-QS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/27