Puls QS10.241 Power Supply Specification Guide

Page of 27
 
 
QS10.241, QS10.241-A1/ -C1/ -D1
 
 
Q-Series 
24V,
 
10A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
5.  I
NPUT 
I
NRUSH 
C
URRENT
 
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short 
input voltage interruptions. 
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Inrush current 
max. 
10A
peak
 10A
peak
 10A
peak
 
over entire temperature range 
 typ. 
5A
peak
 4A
peak
 7A
peak
 
over entire temperature range 
Inrush energy 
max. 
4A
2
s 4A
2
s 4A
2
over entire temperature range 
Inrush delay (A) 
typ. 
650ms 
520ms 
250ms 
 
 
Fig. 5-1   Input inrush current, typical behavior 
 
 
 
Input Current
Input Voltage
Output Voltage
A
 
 
A…. Inrush 
delay 
 
Input:  
230Vac 
Output:  
24V, 10A 
Ambient: 25°C 
Upper curve: 
Input current 2A / DIV 
Middle curve: 
Input voltage 500V / DIV 
Lower curve: 
Output voltage 20V / DIV 
Time basis:  
100ms / DIV 
 
Nov. 2011 / Rev. 2.1 DS-QS10.241-EN 
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
6/27