Puls QS20.241 Power Supply Specification Guide
QS20.241, QS20.241-A1, QS20.241-C1
Q-Series
24V,
20A,
S
INGLE
P
HASE
I
NPUT
14. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available on request.
industry environment without any restrictions. A detailed EMC report is available on request.
EMC Immunity
According generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge
EN 61000-4-2
contact discharge
air discharge
air discharge
8kV
15kV
15kV
Criterion A
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst) EN
61000-4-4
input
lines
output lines
DC-OK signal (coupling clamp)
DC-OK signal (coupling clamp)
4kV
2kV
1kV
2kV
1kV
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L Æ N
L Æ PE, N Æ PE
L Æ PE, N Æ PE
2kV
4kV
4kV
Criterion A
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+ Æ -
+ / - Æ PE
+ / - Æ PE
1kV
1kV
1kV
Criterion A
Criterion A
Criterion A
Surge voltage on DC-OK
EN 61000-4-5
DC-OK signal Æ PE
1kV
Criterion A
Conducted disturbance
EN 61000-4-6 0.15-80MHz
10V
Criterion
A
Mains voltage dips
EN 61000-4-11
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11
0% of 200Vac (=0V)
5000ms
Criterion C
Voltage sags
SEMI F47 0706
dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
1000ms
500ms
200ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Powerful transients
VDE 0160
over entire load range
750V, 1.3ms
Criterion C
Criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply
will occur.
EMC Emission
According generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission
input lines
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22
Class B
Conducted emission
output lines **)
output lines **)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
limits for DC power port acc. EN
61000-6-3 not fulfilled ***)
61000-6-3 not fulfilled ***)
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
fulfilled for class A equipment
Voltage fluctuations, flicker
EN 61000-3-3
fulfilled *)
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) tested with constant current loads, non pulsing
**) for information only, not mandatory for EN 61000-6-3
***) Quasi-peak values fulfilled, average values +5dB
**) for information only, not mandatory for EN 61000-6-3
***) Quasi-peak values fulfilled, average values +5dB
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/26