14.  EMC 
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available on request. 
 
EMC Immunity 
According generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
contact discharge 
air discharge 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
input 
lines 
output lines 
DC-OK signal (coupling clamp) 
4kV 
2kV 
1kV 
Criterion A 
Criterion A 
Criterion A 
Surge voltage on input 
EN 61000-4-5 
L Æ N 
L Æ PE, N Æ PE 
2kV 
4kV 
Criterion A 
Criterion A 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ / - Æ PE 
1kV 
1kV 
Criterion A 
Criterion A 
Surge voltage on DC-OK 
EN 61000-4-5 
DC-OK signal Æ PE 
1kV 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
Mains voltage dips 
EN 61000-4-11 
0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac
 
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 
Voltage interruptions 
EN 61000-4-11 
0% of 200Vac (=0V) 
5000ms 
Criterion C 
Voltage sags 
SEMI F47 0706 
dips on the input voltage according to SEMI F47 standard 
 
 
80% of 120Vac (96Vac) 
70% of 120Vac (84Vac)
 
50% of 120Vac (60Vac) 
1000ms 
500ms 
200ms 
Criterion A 
Criterion A 
Criterion A 
Powerful transients 
VDE 0160 
over entire load range 
750V, 1.3ms 
Criterion C 
Criterions: 
A:    Power supply shows normal operation behavior within the defined limits.  
C:    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 
will occur. 
 
EMC Emission 
According generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  
input lines 
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 
Class B 
Conducted emission  
output lines **) 
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
limits for DC power port acc. EN 
61000-6-3 not fulfilled ***) 
Radiated emission 
EN 55011, EN 55022 
Class B 
Harmonic input current 
EN 61000-3-2 
fulfilled for class A equipment 
Voltage fluctuations, flicker 
EN 61000-3-3 
fulfilled *) 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
*) tested with constant current loads, non pulsing 
**)  for information only, not mandatory for EN 61000-6-3 
***) Quasi-peak values fulfilled, average values +5dB 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
13/26