Chapter 4      Removal and Replacement Procedures
  Removing and Installing the AC-Input Power Supplies
Removing the 1000 W, 1300 W, 2500 W, 3000 W, 4000 W, and 6000 W AC-Input Power Supplies
Warning
Hazardous voltage or energy is present on the backplane when the system is operating. Use caution 
when servicing. 
Statement 1034
To remove an AC-input power supply, follow these steps:
Step 1
Turn the power switch to the Off (0) position on the power supply that you are removing. 
(See
.) Turning the power switch off also disengages a pawl that unlocks the power supply 
from the chassis.
Step 2
Disconnect the power cord from the power source.
Step 3
Loosen the screw on the cable retention device, and disconnect the power cord from the power supply 
being removed. 
Note
The AC power cord for the 4000 W power supply is hard wired to the power supply and cannot 
be removed.
Step 4
Loosen the captive installation screw. (See 
Caution
Use both hands to install and remove power supplies. Catalyst 6500 series AC-input power supplies 
weigh between 14.5 pounds (6.58 kg) and 29.0 pounds (13.15 kg).
Figure 4-6
AC-Input Power Supply Front Panel
Step 5
Grasp the power supply handle with one hand, and slide the power supply part of the way out of the 
chassis. Place your other hand underneath the power supply, as shown in 
, and slide the power 
supply completely out of the chassis.
Step 6
If the power supply bay is to remain empty, install a blank faceplate (Cisco part number 700-03104-01) 
over the opening, and secure it with the captive installation screw.
Power
switch
Cable 
retention
device
AC power
connection
INPUT
OK
FAN
OK
OUTPUT
FAIL
Captive installation
screw
Status LEDs
16029
I
0