Moxa ioLogik E2212 IOLOGIK E2212 User Manual

Product codes
IOLOGIK E2212
Page of 3
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Automation Controllers
ioLogik E2212
Front-end intelligence that supports 24 Click&Go™ rules
 
Active Messaging with real-time stamp, including SMS, 
 
SNMP Trap with I/O status, TCP, and email
Supports SNMPv1/v2c/v3 protocol
 
I/O peer-to-peer function
 
Built-in web console
 
PC utility: Auto detection of installed modules
 
Windows/WinCE VB/VC.NET and Linux C APIs
 
Moxa’s ioLogik E2212 is a new type of active micro controller that 
can be used as an RTU (Remote Terminal Unit). Active Ethernet micro 
controllers are a kind of PC-based data acquisition and control device 
that use proactive, event-based reporting to control I/O devices. Unlike 
traditional RTUs, which are passive and must poll for data, Moxa’s 
Active OPC Server makes seamless connection with SCADA systems 
a reality. In addition, SNMP is used for communicating with an NMS 
(Network Management System) for IT field users. The I/O status of 
an Active Ethernet micro controller can be reported and controlled 
automatically on-site based on user specified conditions. This report-
by-exception approach, which is new to PC-based monitoring, requires 
far less bandwidth than traditional polling methods.
Active Ethernet micro controller with 8 digital inputs, 
8 digital outputs, and 4 DIOs
Introduction
LAN
Ethernet: 1 x 10/100 Mbps, RJ45
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, 
CGI, SNTP
Serial Communication
Interface: RS-485-2w: Data+, Data-, GND
Serial Line Protection: 15 KV ESD for all signals
Serial Communication Parameters
Parity: None
Data Bits: 8
Stop Bits: 1
Flow Control: None
Baudrate: 1200 to 115200 bps
Protocol: Modbus/RTU
Digital Input
Channels: 8, source/sink selectable
Sensor Type: NPN, PNP, and Dry contact
I/O Mode: DI or Event Counter (up to 900 Hz)
Dry Contact: 
• Logic 0: short to GND 
• Logic 1: open
Wet Contact:
     
Common Type: 6 points per COM 
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Over-voltage Protection: 36 VDC
Poweroff Counter: Supports poweroff counter storage function
Digital Output
Channels: 8, sink type, 36 VDC, 200 mA
I/O Mode: DO or Pulse Output (up to 100 Hz) 
Pulse Wave Width/Frequency: 10 ms/100 Hz
Over-voltage Protection: 45 VDC
Over-current Limit: 400 mA (typical)
Over-temperature Shutdown: 175°C (min.)
Output Current Rating: Max. 200 mA per channel
Isolation: 2K Vrms or 3K VDC (Magnetic)
DI/DO Configurable Channels
Channels: 4
I/O Mode: 
• DI or Event Counter (up to 900 Hz) 
• DO or Pulse Output (up to 100 Hz)
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Power Consumption: 282 mA typical @ 24 VDC
Physical Characteristics 
Wiring: I/O cable max. 14 AWG
Dimensions: 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
Weight: under 250 g
DI Type
Status
Source
Sink
ON
0 to 3 VDC
10 to 30 VDC
OFF
10 to 30 VDC
0 to 3 VDC
Specifications