RadioFrame Networks Inc DH2 User Manual

Page of 164
RadioFrame System 
Pre-Installation 
RFN_3.1 Beta
  
35 
System 
Unit 
Weight 
 
iSC-3  (2) 
 
 EAS 
 
 CSU 
 
Power Plant 
Rectifier 
72 lbs  
(Power Plant 58 lbs) + (two Rectifiers at 7 lbs ea.) 
 Battery 
600 
lbs 
(eight batteries at 75 lbs each) 
3.3.4 Power 
System 
Unit 
Power 
RadioFrame System 
NCU 
 
100-240 Volts AC, 47-63 Hz, 8-3.5A, or  
 
Negative 52.5 ±.5 Volts DC, 11A 
 ACU 
 
100-240 Volts AC, 47-63 Hz, 8-3.5A, or  
 
Negative 52.5 ±.5 Volts DC, 11A 
iDEN Interface 
iSC-3  (1) 
 
Negative 40-60 Volts DC; 1.5 A 
 
iSC-3  (2) 
 
Negative 40-60 Volts DC; 1.5 A 
 EAS 
 
Negative 40-60 Volts DC 
 CSU 
 
Negative 40 Volts DC 
Power Plant 
Rectifier 
Input 
  
Voltage 
 
85 to 265 VAC (continuous) 
 
45 to 70 Hz 
  
Current 
 
12 Amp maximum 
The rectifier’s micro-controller adjusts 
the output current to limit the input 
current to allow each rectifier to be 
plugged into a standard 115/230 VAC @ 
15 Amp IEC outlet. 
 
 
Power Factor 
>90% for 20% to 100% loads 
 
 
Output 
  
Voltage 
 
50.00 to 60.00 VDC 
 
52.5 VDC Factory Set (default) 
  
Regulation 
 
± 1.0% (includes output o-ring diode) 
  
Overvoltage 
 
50.00 to 60.00 VDC 
 
57.00 VDC Factory Set (default) 
 
RED [FAIL] LED indication and shuts 
down rectifier providing output 
current. 
  
Noise 
 
<32 dBmC (voice frequency) 
 
<100 millivolts-RMS (wide band) 
 
<250 millivolts peak-to-peak