Method of Procedure 
Pre-Installation 
40 
RFN_3.1 Beta
 
AC power cords longer than necessary may be looped down and back up a
 
rack 
or cabinet. Excess lengths of AC power cord shall not be coiled on top of racks or 
cabinets. 
3.3.10.3  Protecting cables within racks and cabinets 
Grounding conductor tap joints shall be installed in order to prevent the 
conductor or connection device from coming in contact with metallic surfaces. 
Where cables or conductors are routed through holes in metallic surfaces or near 
sharp edges, the sharp surfaces shall be suitably protected with a grommet or 
similar material to help protect the cable or conductor from damage caused by 
sharp edges. 
3.3.10.4  Cable bending radius within racks and cabinets 
Grounding conductors of all sizes shall maintain a minimum bending radius of 8 
in. (20 cm). The angle of any bend shall be not less than 90°. 
The bending radius of CAT 5 cables shall be not less than 10 times the outside 
diameter of the cable. Follow the cable manufacturer's recommendation and refer 
to ANSI/TIA/EIA-568 and CSA-T529 for additional information. 
All other cables shall not have sharp bends that will damage or degrade the 
performance of the cable. The cable manufacturer's specifications shall be 
followed. 
3.3.10.5  Cable separation and grouping within racks or cabinets 
Cabling in racks or cabinets shall be grouped according to function. 
Cable groups within racks and cabinets shall be separated by a minimum of  
2 in. (5.1 cm) from other cable groups. Refer to ANSI/TIA/EIA-568a and -569; 
and NFPA 70, Articles 800-52, 810-18, and 820-52 for more information. 
3.3.11 Alarm 
Blocks 
All alarm wires shall be tagged and labeled with the appropriate alarm item. 
All 
contacts will be normally closed, dry, and isolated from ground. Alarm wire will be 
neatly run and secured using nylon cable ties/clamps every three feet to walls 
and existing cable tray. All alarm wiring shall be two-wire, 22 AWG. 
3.4 Remote 
ACUs 
Up to seven remote ACUs may be installed for a total of 8 ACUs per NCU.