RadioFrame Networks Inc DH2 User Manual

Page of 164
RadioFrame System 
Pre-Installation 
RFN_3.1 Beta
  
41 
3.4.1 Mounting 
Remote ACUs are located in telco rooms or other closets throughout the building, 
mounted in 19” EIA-standard compliant racks or equivalent. Any other method 
used to mount the remote ACU is not approved, and could void the warranty on 
the product and other components in the RFS. 
NOTE:  The ACU may be placed on a flat surface only if the front and back of the 
unit are accessible and if the side vents are not blocked. In this case, the ACU is 
not secured and, therefore, is not rated to withstand any level of earthquake, and 
the warranty may be voided.  
Currently, the remote ACU does not include a Universal Power Supply (future 
enhancement). Grounding of the remote ACU is not required by RadioFrame 
Networks and is the responsibility of the RFN customer or its customer. A 
bonding ground point for protective earth grounding is provided; #6 screw with 
internal sems washer. 
3.4.2 Clearances 
• 
Dimensions: 19" wide x 7" high x 13" deep (approx.) 
3.4.2.1 Back 
• 
7” 
3.4.2.2 Front 
• 
12” 
3.4.2.3 Sides 
• 
Left side (facing unit): 0”; right side: 2” 
3.4.2.4 Above 
• 
Above: 0” 
3.4.3 Weight 
• 
27 lbs (fully loaded) 
3.4.4 Power 
• 
100-240 Volts AC, 47-63 Hz, 8-3.5A , or 
• 
Negative 48-56 Volts DC, 11A