RadioFrame Networks Inc MCSERIES10 User Manual
MC-Series System Installation & Testing
Scheduled and Unscheduled Maintenance
90
RadioFrame Networks, Inc.
2
Select the Upload Serial Log w/ IP Address button, and in the pop-up window, enter the IP
address of the component, and the select OK. Refer to Appendix B: Default IP Addresses.
address of the component, and the select OK. Refer to Appendix B: Default IP Addresses.
Alternately, the component can be selected from the dropdown menus, though RadioFrame
Networks recommends using the IP address method.
Networks recommends using the IP address method.
3
Copy the contents of the serial log window into a text file, and save the text file.
4
Email the text file to the Technical Assistance Center at:
7.7 Power Down Procedure
When powering down the entire MC-Series System, follow these instructions.
1
Using the breakers on the PDU, power off equipment in the MC-Series System rack in the
following order:
following order:
•
BIC
•
AIC
•
RBS 1 (RBS 2 and RBS 3 if present)
•
RF Shelf 1, RF Shelf 2, and RF Shelf 3