Senstar Corporation LM100 User Manual

Page of 74
Installing the LM100 gateway
Page 34
Senstar LM100 Product Guide
Gateway wiring connections
LM100 gateway wiring connections are made on removable terminal blocks. The screw terminals 
accept wire sizes from 12 to 24 AWG, with a 6.4 mm (¼ in.) strip length. Remove the terminal 
blocks to make the wiring connections. Reinstall the blocks after the connections are complete, 
and verified. 
 shows the gateway input wiring connections. 
 and 
illustrate the gateway wiring connections and the connections to the I/O option cards. 
to 
 show the Silver Network wiring options.  
Figure 35: Gateway input wiring examples
Note
See instruction sheet 00DA1503 for information about installing the 
optional relay output card and dry contact input card.
NO inputs unsupervised
NO input 
dual resistor supervision
NC input 
cut and short supervision
cut and short supervision
dual resistor supervision
NC inputs unsupervised
single resistor supervision
single resistor supervision
cut supervision
short supervision
NO input 
NC input