Senstar Corporation LM100 User Manual
Installing the LM100 gateway
Senstar LM100 Product Guide
Page 33
Relay contact ratings
The gateway’s relays are latching, and are rated for 30 V @ 1 A max. In Remote control mode, you
can configure the relays as latching (ON by command, OFF by command), in flash mode (ON-
OFF-ON-OFF... by command, then OFF by command), or pulse mode (ON for a period, then
OFF). For flash and pulse modes, the relay Active/Inactive times are selectable.
can configure the relays as latching (ON by command, OFF by command), in flash mode (ON-
OFF-ON-OFF... by command, then OFF by command), or pulse mode (ON for a period, then
OFF). For flash and pulse modes, the relay Active/Inactive times are selectable.
In Local control mode the relays remain active for the event’s duration or for the selectable Hold
Time, whichever is longer.
Time, whichever is longer.
Auxiliary inputs
I/O points defined as inputs are voltage sensing inputs. The gateway determines an input’s status
via an internal reference voltage, and the configuration of the contact closures and supervision
resistors.
via an internal reference voltage, and the configuration of the contact closures and supervision
resistors.
provides wiring diagrams for auxiliary device inputs.
In Local control mode the inputs are used to activate luminaire zones. When the input goes high,
the specified luminaire zone is activated.
the specified luminaire zone is activated.
In Remote control mode the AUX inputs serve as inputs to the host SMS for reporting the status of
auxiliary security equipment.
auxiliary security equipment.
Figure 34: Gateway output schematics
CAUTION
The contact closure inputs to the gateway MUST be voltage-free.
power sourcing output
dry contact output
shunt
Form A
Form B
high side drive
Form A
Form B
power sinking output
power sinking output
dry contact output