Sequencing the heads
Page 52
Senstar LM100 Product Guide
Compiling the Unordered Heads list
1. Establish a UCM connection to the gateway (USB or TCP/IP).
2. On the Config tab, select the Sequence button.
3. Select the Record button below the Unordered Heads table and wait for the LM100 gateway to 
compile the list of unordered heads (this process can take several minutes). 
4. Select the Stop button once the compiled list is displayed in the Unordered Heads column.
Verify that all of the installed luminaires have been added to the list to ensure that each 
luminaire in the system is communicating properly (e.g., If there are 38 luminaires in your 
Senstar LM100 system there should be 38 luminaires in the unordered list.)
If the unordered list is incomplete, repeat this process extending the wait time, before selecting 
the stop button. If the list is still incomplete, you must determine which head is not 
communicating, and rectify the situation.
5. Proceed to 
Compiling the Ordered Heads list
Location testing is done to identify the physical location of each installed luminaire. Each luminaire 
is moved from the Unordered Heads list into the Ordered Heads list in the order that the tests are 
conducted. To do the location testing, use a screwdriver (or a length of wood like a broomstick) to 
strike the shaft of the luminaire (if it is not possible to strike the luminaire’s shaft, strike the fence 
post on which the luminaire is mounted). Strike the shaft once firmly, to register the luminaire in the 
Ordered Heads list. This will cause the luminaire to flash twice, pause for a second, and then flash 
three times to indicate the luminaire has been moved into the Ordered Heads list. In the Ordered 
Heads list, the luminaire is identified by a number indicating the test order and by its 5-digit 
network Id (see 
). 
If the luminaire flashes 4 times, this indicates that a second luminaire has also detected the 
location test event. In this case, repeat the procedure using less force when striking the shaft. 
If the luminaire flashes 5 times, this indicates that the luminaire is already included in the Ordered 
Heads table. In this case, proceed to the next luminaire and continue the location testing.
1. Select the Record button below the Ordered Heads table and proceed to the designated first 
luminaire (usually the luminaire AP).
2. Strike the shaft of the first luminaire firmly once.
The luminaire will flash twice pause and then flash three times.
The number one and the luminaire’s 5 digit Id are displayed at the top of the Ordered Heads 
list.
3. Proceed to the second luminaire and strike the shaft of the second luminaire once.
The luminaire will flash twice pause and then flash three times.
The number two and the luminaire’s 5 digit Id are displayed on the second line of the Ordered 
Heads list.
4. Proceed around the perimeter doing a location test at each luminaire, thereby, moving each 
luminaire to the Ordered Heads list in the desired sequence. 
5. After conducting the test at the final luminaire on the perimeter, return to the UCM computer 
and select the Stop button.
6. The Ordered Heads table is now populated by luminaires in the same order that the location 
tests were done.
7. Proceed to 
.
Tip
Use a site plan and mark the number down (from the test order) beside 
each luminaire’s location as the tests proceed.