Senstar Corporation LM100 User Manual

Page of 74
Input/output configuration
Page 64
Senstar LM100 Product Guide
Input configuration procedure
1. Select the Aux Cfig tab on the UCM window.
2. From the Supervision drop down, select the desired supervision scheme for the input.
3. Select the Resistor 1 value, if applicable.
4. Select the Resistor 2 value, if applicable.
5. Set the Noise Tolerance, if required.
6. Set the Line Drop, if required.
7. Set the Filter Window.
8. For Local Control mode, specify the luminaire zone to activate when the input is activated.
9. Repeat this procedure for each input.
10. Save the UCM configuration file and download the configuration changes to the gateway.
Output relays
   
Output relay setup (Local control mode)
In Local control mode, the Aux outputs are setup via the Local Aux Control Activation check boxes 
to report alarm and supervision conditions. The outputs are then controlled by the gateway to 
activate on the user-specified conditions. The outputs remain active for an event’s duration or for 
the selectable relay Active Time, whichever is longer.
1. Use the Output selection arrows to select a relay.
2. Select the relay’s function: high side drive power sourcing; Form A (N.O.) or Form B (N.C.) 
power sinking (up to 100 mA power sourcing/sinking); or dry contact Form A or Form B.
3. Specify the Hold/Active Time parameter.
4. Specify the conditions from the Local Aux Control Activation field under which this relay will 
activate. Zone alarms are assigned on the segment setting window on the Config tab.
5. Repeat this procedure for each defined output.
6. Save the UCM configuration file and download the configuration changes to the gateway.
Output relay setup (Remote control mode)
In Remote control mode, the relays are controlled by the host SMS to operate auxiliary equipment 
as output control points (e.g., to activate lights, doors, sirens, CCTV equipment, etc.). The relays 
are configured to respond to commands from the host computer. Configure the relays as latching 
(ON by command, OFF by command) or in flash mode (ON-OFF-ON-OFF etc. by command, OFF 
by command) or in pulse mode (ON for a period, then OFF). For flash and pulse modes, the ON-
OFF time duration is configurable.
CAUTION
The I/O port configuration jumpers must be correctly set according to 
the specific function of each port (see 
).
Note
The four outputs on the ROC are Form C (selectable as N.O. or N.C.). 
The ROC outputs cannot source or sink power.
Note
To use the onboard relays, the gateway ports must be configured as 
outputs via the Aux Type radio buttons.
Note
To assign relays to specific zones, see 
.