Remote light activation
In both local control mode and remote control mode, the LM100 can be configured to have specific 
luminaires activated from remote locations. In local control mode, a simple on/off switch in a 
central control room can be connected to an Aux input on the gateway. When the switch is turned 
on the aux input goes high and the luminaire zone that is specified to activate in response turns on 
(Zone Light Activate on the Aux Config tab). In remote control mode a command from the host 
SMS can activate a luminaire zone.
Input wiring configurations
 includes the selectable Aux input wiring configurations, and 
 includes the 
selectable supervision resistor values.  
CAUTION
The I/O port configuration jumpers must be correctly set according to 
the specific function of each port (see 
).
Note
Use ¼ W 1% supervision resistors (se
 for recommended 
resistor values).
Input option
UCM selection
Alarm relay Supervision
R1
R2
unsupervised
NO
---
---
---
single resistor 
supervision
NO
cut
5.1 k
---
dual resistor 
supervision
NO
cut & short
4.3 k
820
unsupervised
NC
---
---
---
single resistor 
supervision
NC
short
5.1 k
---
dual resistor 
supervision
NC
cut & short
5.1 k
820
Table 2: Selectable input configurations
R1 values (single resistor 
supervision)
R1 values (double resistor 
supervision)
R2 values (double resistor 
supervision)
820
1.1 k
820
1 k
2.2 k
1.1 k
1.1 k
4.3 k
2.2 k
1.2 k
4.7 k
3.3 k
1.5 k
5.1 k
5.6 k
2.2 k
5.6 k
3.3 k
4.7 k
5.1 k
5.6 k
Table 3: Selectable resistor values
A
1
A
S
1
2
A
S
A
1
2
A
S