Mode-3: Alarm Reminder Non-Latching 
Same as Mode 1 except, the alarm is re-started if the INPUT is not cleared. Periodically re-starts the 
alarm sequence for situations in which a persisting alarm condition may be overlooked (such as an 
alarm sequence that starts during unstaffed hours and does not self-clear). If alarm state persists more 
than XXX minutes (XXX specified by CU-based variable in the range of 15 to 999 minutes; default is 30 
minutes), then repeatedly re-start this sequence from the beginning as a new alarm.
Mode-4: Alarm Reminder Latching 
Same as Mode 2 except, the alarm is re-started if the corresponding front panel button is not pressed. 
Periodically re-starts the alarm sequence for situations in which a persisting alarm condition may be 
overlooked (such as an alarm sequence that starts during unstaffed hours and does not self-clear). If 
alarm state persists more than XXX minutes (XXX specified by CU-based variable in the range of 15 to 
999 minutes; default is 30 minutes), then repeatedly re-start this sequence from the beginning as a new 
alarm.
Mode-5: Director Buttons Latching 
Four Button Director Call Box; the four external INPUTS are disabled. 
When user presses any of buttons 1 through 4, an alarm SET is broadcast and the corresponding  
LED will flash according to “LED Sequence 1”. (Indicated below.) Responding user presses the front 
panel button “A” (RESPOND) to clear all active alarm(s); an alarm RESET is broadcast and the 
corresponding LED(s) will turn off. If RESPOND button is not pressed within 10 minutes, the call box 
terminates “LED Sequence 1” and the alarm will timeout. 
Mode-6: Alarm Notify & Director Latching 
Provides a combination of External Inputs and Director Buttons: 
INPUTS 1 and 2 operate in Mode 2; the corresponding front panel button must be pressed to RESET.  
Buttons 3 and 4 operate in Mode 5; button “A” is used to RESET active alarms on Buttons 3 & 4. 
LED Sequence-1 
x  LED lights solid for the duration that the input alarm exists for a maximum of 5 seconds.
x  LED continues flashing rapidly for 2-minutes.
x  LED continues flashing in short bursts indefinitely.
x  LED ends the flash sequence with two long flashes, then extinguishes when:
Non-latching Operating Modes - the alarm condition clears.
Latching Operating Modes – when associated RESET is pressed, (if the input alarm condition is  
clear).