Selex Sistemi Integrati Inc. VOR2 User Manual

Page of 254
Model 1150A DVOR 
 
Rev. -  November, 2008 
 
This document contains proprietary information and such information may not be disclosed 
to others for any purposes without written permission from SELEX Sistemi Integrati Inc. 
2-45
2.3.2.14.1.9 LCU Transfer Control State Machine #1 and #2 and Discrete Controls
The  heart  of  the  LCU  is  the  two  redundant  transfer  control  state  machines.    These  are  configured  by  the  RMS; 
receive  key  commands  from  the  front  panel  or  from  the  RMS,  and  process  alarms  reported  by  the  monitors  after 
being  filtered  by  the  Positive  and  Negative  Alarm  Registers.    Once  configured  for  on  air,  the  state  machines  will 
drive out the required signals to enable the transmit on clocks (1_TX_ON_CLK, 2_TX_ON_CLK), enable the +24V 
power to the synthesizer VCO's (1_24VCO, 2_24VCO), and select the required system to be placed on the antenna 
(1_+24ANT_SW, 2_+24ANT_SW).   
 
With the redundant state machines, detection of an error assures that the system generating the error will be removed 
from the air.  The LCU transfers to the standby system if configured to do so either immediately for a hot Standby 
system or after a 20 second delay for a cold Standby system.  If further alarms are detected, the LCU transfer state 
machines will shut the standby transmitter down and block any further transmission for a minimum of 20 seconds.  
Restarts are under the control of the RMS. 
 
The LCU transfer control  state  machines report status back to the RMS indicating the state of the  state  machines, 
and any shutdowns that have occurred.  The LEDs on the front panel reflect the current state of the state machines.   
 
2.3.2.14.1.10 LED Control
Status  is  fed  back  to  a  local  operator  via  the  LED's  on  the  front  panel  of  the  LCU.    These  reflect  the  state  of  the 
transmitters and the various alarms as reported by the monitors. 
 
2.3.2.14.1.11 Audible Alarm
If an alarm as reported by the monitors is detected that is not bypassed, the audible alarm is generated.  The audible 
alarm  can  be  reset  by  pressing  the  Alarm  Silence  button  on  the  front  panel.    In  local  mode,  the  audible  alarm  is 
disabled. 
 
2.3.2.14.1.12 Monitor Alarm Interface
In order to insure that a monitor alarm signal is communicated to the control logic, redundancy is incorporated into 
the monitor alarm signals.  Each alarm signal is sent as two signals, one active high and the other active low.  In the 
LCU, resistors are used to pull each of their signals to their active (alarm) state.  This insures that an alarm condition 
will be sensed if there is an open in either alarm line.  If an alarm line is shorted to its inactive (non-alarm) state, the 
other line will communicate an alarm condition.  If the 1_INT_ALARM+ signal is disconnected, a resistor will pull 
the  input  high  resulting  in  an  alarm  condition  being  sent  to  the  control  logic  in  the  EPLD  U3.    If  the 
1_INT_ALARM- signal is disconnected, a resistor will pull the input to a low logic level.   
 
2.3.2.14.1.13 Station Control Logic
The station control logic is duplicated in both U1 and U3.  The logic responds to local operator control through the 
pushbutton switch inputs as well as remote control through the parallel interface.  The local operator can perform the 
following functions: 
 
a. 
Specify which VOR transmitter is to be designated as main. 
b. 
Turn either transmitter ON and connect it to the antenna. 
c. 
Turn either transmitter ON and connect it to the load. 
d. 
Turn either transmitter OFF. 
e. 
Toggle the bypass state of either of the monitored signal sources (Integral, Standby). 
f. 
Silence the aural alarm (until the next event causes it to sound). 
g. 
Toggle the state of local control.  When local control is set, input from the keypad is enabled.