Identifying failures on the primary and/or secondary side  
Primary and/or Secondary side failure is indicated by any of the following conditions: 
  Ethernet LC link down, as indicated on the Reader browser Status page. 
  Ethernet IR network link down, as indicated on the Reader browser Status page. 
  Primary CTM MC or CGC 
LED
s are red  
  Serial LC link down, as indicated on the Reader browser STATUS page 
Primary side failure is indicated by any of the following conditions 
  SPM switch is in PRIMARY position: primary CTM ACTIVE 
LED
 is red 
  SPM switch is in AUTO position: primary CTM ACTIVE 
LED
 is red 
Secondary side failure is indicated by any of the following conditions: 
  SPM switch in any position: secondary MC or CGC 
LED
s are red  
  SPM switch is in SECONDARY position: secondary CTM ACTIVE 
LED
 is red 
  SPM switch is in AUTO position: primary CTM ACTIVE 
LED
 is red and secondary CTM ACTIVE 
LED
 is red. 
Events that cause an automatic switchover  
Table 6-4 outlines the situations that can cause an automatic switchover and what settings need to be 
configured for the trigger to be enabled. 
Table 6-4: Switchover triggers 
Event 
Cause 
Enabling 
Failed CGC Health 
The Reader continuously monitors the CGC 
health and forces a switchover if health fails.  
Automatic 
Failed Serial Lane 
Controller Link 
 
The Reader forces a switchover when an 
enabled serial link from the LPM to the LC 
has been interrupted. Usually a downed link 
is due to external conditions. 
Only the lack of OBU transactions in outgoing 
messages to the LC allows a downed link to 
be detected. To detect serial cable issues in 
the absence of OBU transactions, the 
operator must enable Heartbeat messages  
Must enable Switchover on 
Serial Link Down from 
General tab on 
Configuration page 
Must set LC Retry Timeout 
from 
Serial tab on 
Configuration page 
Set Heartbeat messages from 
LC tab on Configuration 
page