Digital Security Controls Ltd. 00NB9001 User Manual

Page of 34
16
defined as “Interior Delay” will go into alarm instantly. 
When the system is stay armed, this zone will be active, 
but when it is tripped, it will initiate the entry delay.
[87]
Delayed 24 Hour Fire (Wireless):   If this zone is vio-
lated (e.g. the smoke detector senses smoke), the alarm 
will immediately sound, but the alarm communication to 
the central station will be delayed for 30 seconds. If dur-
ing the 30 second delay the user presses the [#] key, the 
alarm and communicator will be delayed an additional 90 
seconds. This provides time for a user to correct the prob-
lem. 
NOTE:
 If a second Fire zone is violated, or if the Fire keys 
are pressed during the delay time, the panel will latch the 
alarm output and communicate immediately.
[88]
Standard 24 Hour Fire (Wireless):   When this zone is 
violated (e.g. the smoke detector senses smoke), the 
panel will immediately latch the alarm output and com-
municate to central station. The alarm will sound for the 
Bell Cutoff time programmed in Section [005], or can be 
programmed to sound until a valid code is entered (Sec-
tion [014], Option [8]).
5.2
Zone Attributes
Each zone will operate according to the Zone Definition selected 
for it (see section 5.1 “Zone Definitions” on page 15).
You can customize the operation of a zone for a specific applica-
tion by changing the zone attributes. The following attributes are 
programmable by zone:
NOTE:
 Do not change attributes for Fire Zones from the 
default settings.
• Audible/Silent   Determines whether the zone will activate 
the alarm output or will be silent.
• Pulsed/Steady   Determines if the alarm output will be 
steady or pulse on for 1 second and off for one second.
• Activate Chime   Determines if the zone will activate the 
chime feature (see section  “[*] [4] Door Chime On/Off” on 
page 11).
• Bypass Enable   Determines if the zone can be manually 
bypassed (see section  “[*][1] Zone Bypassing” on page 10).
• Force Arm Enable   Determines if the system can be armed 
with the zone violated. At the end of exit delay, if this type of 
zone is violated, it will be ignored by the system. Once the 
zone is secured it will be added back into the system.
This zone attribute is useful for a garage door. The customer 
can arm the system with the garage door open. Later when 
the customer closes the door it becomes part of the system. 
NOTE:
 24-hour zones must not have Force Arm enabled.
• Swinger Shutdown Enable    Determines if the system will 
shut down the communicator for the zone after the swinger 
limit is reached (see section 5.18 “Swinger Shutdown” on 
page 23).
• Transmission (TX) Delay Enable   Determines if the system 
will delay communicating the alarm reporting code to the 
central station (see section 5.12 “Communicator - Reporting 
Codes” 
on page 20). 
• Wireless Zone   Determines if the zone is a wireless zone or a 
hardwired zone. Allows the system to generate low battery 
trouble and zone supervisories.
NOTE:
 The wireless zone attribute must be enabled for all 
enrolled wireless zones. 
Audible/Silent Alarm. . . . . . .  Section [101] to [132], Option [1]
Pulsed/Steady Alarm . . . . . . .  Section [101] to [132], Option [2] 
Activate Chime. . . . . . . . . . .  Section [101] to [132], Option [3] 
Bypass Enable. . . . . . . . . . . .  Section [101] to [132], Option [4] 
Force Arm Enable . . . . . . . . .  Section [101] to [132], Option [5] 
Swinger Shutdown Enable . .  Section [101] to [132], Option [6] 
Transmission Delay Enable  . .  Section [101] to [132], Option [7]
Wireless Zone . . . . . . . . . . . .  Section [101] to [132], Option [8]
5.3
Enrolling Hardwired Zones
You can install up to two hardwired zones on the NT9010 sys-
tem. To make the wiring connections for these zones, please see 
section 2.3 “Zone Wiring” on page 3. You must also enroll the 
hardwired zones on the system. 
To do this, in the Installation Wizard enter serial number 
[200001] for the first hardwired zone, and [200002] for the sec-
ond hardwired zone. The NT9010 system will automatically 
assign the hardwired zone to the next available zone number. 
If you need to change the zone assignment of the hardwired 
zones, you can do this in the Advanced programming sections:
1. Enter programming section [807].
2. Enter sub-section [091] for the first hardwired zone, or sub-
section [092] for the second hardwired zone.
3. Enter the 2-digit number of the zone that will be hardwired. 
NOTE:
 Entering a zone as a hardwired zone will override 
any wireless device serial number that may be programmed 
for the zone.
NOTE:
 Fire zones are not supported as hardwired zones.
5.4
Wireless Device Serial Numbers
Normally, you will use the NT9010 Installation Wizard to enter 
device serial numbers. If you need to delete a device from a zone, 
or replace a device, you can use the advanced programming sec-
tion. To add, replace, or delete devices:
1. From Installers’s Programming, enter section [804]
2. Enter the 2-digit number of the zone you want to delete (01 - 
32). The system announces the current serial number for the 
zone.
3. Enter the new serial number for the zone. To delete a device, 
enter [000000]. The wireless device for the zone will be 
removed.
NOTE:
 You may need to remove power from the system 
and then restore it to clear troubles caused by deleted 
zones.
5.5
Wireless Zone Supervision
NOTE:
 The RF Jam Detect zone, hardwired zones, and Panic 
Pendants must have the supervision option disabled.
Wireless Supervisory Window
Each wireless zone will send a supervisory signal every 12 min-
utes. If the receiver does not receive a signal within the time pro-
grammed for the Wireless Supervisory Window, it will 
generate a supervisory fault. 
To program the wireless supervisory window, from Advanced Pro-
gramming: