2.3.22 Walk Test
The Installer Walk Test can be used to test the alarm state of each zone of the 
system. Before beginning the walk test, ensure the following conditions are met:
1. The system is disarmed
2. The Keypad Blanking option is disabled (section [016]: [3])
3. The Fire Bell is Continuous option is disabled (section [014]: [8])
4. The Transmission Delay is disabled, if Transmission Delay is not required (section 
[370])
NOTE:
 Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
1. Enter Advanced Programming
2. Enter Section [901]
When any zone is violated the system will activate the Bell Output for two seconds, 
log the event to the Event Buffer and communicate the alarm to the central station. 
Each zone should be tested several times during the test. Check the event buffer to 
ensure that all zones and FAP keys are functioning properly.
NOTE:
 The transmission delay timer will affect the communication of 
events during walk test mode.
To stop the test, you must do the following:
1. Enter Advanced Programming
2. Enter Section [901]
Zones do not have to be restored to stop the test.
NOTE:
The Alarm Memory is cleared upon entering Walk Test mode.