C h a p t e r   2 :   A d v a n c e d   P r o g r a m m i n g
5 4
2.3.17 Event Buffer
The system will store the last 128 events that have occurred on the system. Each 
event will contain the time, date, and the event itself along with the zone number, 
access code number or any other information pertaining to the event.
If the Event Buffer Follows Swinger Shutdown feature is enabled the event 
buffer will not store events after the swinger shutdown level has been reached. This 
will prevent the system from overwriting the entire buffer if a problem exists (see 
2.3.18 Swinger Shutdown on page 54).
The event buffer can be uploaded to a computer for viewing through the DLS software.
Event Buffer Follows Swinger Shutdown  . . . . . . . . . . . . .  Section [013], Option [7]
2.3.18 Swinger 
Shutdown
The swinger shutdown feature is designed to prevent a runaway communicator 
from tying up the central station. Different limits can be programmed for Zone 
Alarms
Zone Tampers and Maintenance signals. After the system has commu-
nicated the programmed number of transmissions for an event it will no longer 
report that event until the swinger shutdown is reset.
For example, the swinger shutdown limit for Zone Alarms is set to [003]. The sys-
tem will not send more than 3 alarm signals for each zone with a swinger attribute 
until the swinger shutdown is reset.
The Bell output will not be activated for alarms on zones that have exceeded the 
limit of alarms set in the Swinger Shutdown counter.
Swinger Shutdown will be reset when the system is armed, or every day at mid-
night. Once reset, the system will again communicate normally.
Swinger Shutdown Limit (Alarms/Tampers/Maintenance) . . . . . . . . . . Section [370]
2.3.19 Timebase
In cases of unstable AC power input you can use the internal crystal to keep a more 
accurate timebase by enabling the Timebase is Internal Crystal option. 
If the AC power input is very stable it can be used as the timebase, by enabling the 
Timebase is AC line
 option.
Timebase Internal Crystal/AC line  . . . . . . . . . . . . . . . . . . . . . . . . Section [701]: [2]
2.3.20 Factory 
Default
On occasion it may be necessary to return the NT9010 system to factory default set-
tings. You can either default all the programming in the NT9010 (including device 
serial numbers), or you can default only certain sections of the programming. 
Performing a Software Default of the NT9010 System
This procedure will return all NT9010 system programming to the factory default 
settings.
1. Enter [✱][8][Installer’s Code].
2. Enter programming section [999].
3. Enter the Installer’s Code.
4. Enter programming section [999] again.