4.1 Program Zones and Partitions
Now that you have enrolled the wireless devices, you should complete all zone
programming on the system. Although the exact programming required varies de-
pending on which control panel the RF5501-433 is connected to, you should check that
the following programming areas are completed correctly for each wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming sections
[201]-[209]).
• Program the definition for each zone (programming sections [001]-[004]).
NOTE: WLS906 wireless smoke detectors must be assigned to zones defined as Delay
24-hr fire (wireless) [87] or Standard 24-hr fire (wireless) [88] for proper supervision.
• Enable the wireless zone attribute for each wireless zone (PC580, PC1555, PC5008,
PC5010 v2.0 and higher, PC5020, PC5015 v2.2 and higher only) (programming
sections [101]-[132]).
See your system 
Installation Manual, for more information on each of the above
programming sections.
4.2 Enable Receiver Supervision
The control panel will automatically supervise the  receiver via the Keybus one-minute
after at least one device has been enrolled on the module. The system will generate
a General System Supervisory trouble if the module is removed from the Keybus. If you
need to remove the RF5501-433 from an existing system, you will have to disable
supervision of the PC5132.
4.3 Enable Supervision of Wireless Zones
NOTE(for PC5010 v1.x control panels only): For UL Listed installation, Double EOL
resistors must be enabled in the PC5010 for the wireless zones to be supervised. If
normally Closed or Single EOL resistors are selected the PC5010 will not be able to
supervise the wireless devices. If a wireless device stops sending a supervisory sig-
nal (the unit stops functioning) the panel will not indicate a supervisory trouble condi-
tion unless Double EOL resistors are used. In addition, all hardwire zones must be
wired for Double EOL resistors. For more information, refer to your PC5010 v1.x In-
stallation Manual.
NOTE (PC5010 v2.0 and higher, PC5015 v2.2 and higher, PC5020, PC5008, PC1555,
PC580 only): For wireless supervision to work, you must enable the wireless zone at-
tribute on all wireless zones (sections [101] to [132], option [8] ON).
NOTE: The RF Jam Detect zone must have the supervision option disabled.
Wireless Supervisory Window
Each wireless zone  (WLS904P, WLS906,  WLS907, WLS912, WLS914, WLS925L) will send
a supervisory signal every 64 minutes. If the receiver does not receive a signal within the time
programmed for the Wireless Supervisory Window, it will generate a supervisory fault.
 
4