[21] System Event Communication Options
NOTE: Section [20], Option [7] must be enabled for these events to be communi-
cated.
Option 1 - Input Supply Failure
All Modes
If AC power is absent or if DC power drops below 8.8V
DC  
on the RED and BLK
terminals, a
 
trouble will be sent after the delay programmed in section [22] has
expired.  Default - ON,
Option 2 - Low Battery
All Modes
If the battery voltage drops below 5.72V
DC
 a trouble will be sent to Connect 24.
When the battery voltage rises to 5.87V
DC
 the system will send a restore. 
Default - ON.
Option 3 - Skyroute CL3050 Tamper
All Modes
Removing the cover on the Skyroute CL3050 will send a tamper reporting code
to Connect 24Default - OFF.
Option 4 - PC5108 Module Fault
Mode 3
Indicates a Keybus communications fault condition.  Default - OFF.
Option 5 - PC5108 Tamper
Mode 3
Removing the cover on the PC5108 will send a tamper reporting code to
Connect 24.  Default - OFF.
Option 6 - TLM Trouble Report
All Modes
Indicates a telephone line trouble if a CL3050 communications zone is violated.
Default - OFF.
[22] Input Supply Fail TX Delay
All Modes
This value determines the delay (default 0700 = 7 hrs) before an input supply fail-
ure reporting code is sent if programmed.  See Section [21], Option [1] and Sec-
tion [20], Option [2]. Default - 0700 (=7 hrs)
[23] Generic Zone Reporting Timer
Modes 2, 3
This hex value determines the delay before a generic zone reporting code is sent,
if programmed in Section 20 Option 8.
NOTE:  There are four separate timers for Burglary, Fire, Panic and Supervisory;
the delay programmed is the same for each timer.
Default
 - 1E (300 seconds / 5 minutes) Range equals 01-FF Hex seconds x 10
[24] Number of Attempts
All Modes
This value determines how many attempts are made to send an event to
Connect 24.    Default - 03
NOTES:  For UL Installations in Mode 2, minimum 5, maximum 10 attempts
required.
For UL Installations in Mode 3, the combination of attempts between DACT and
Skyroute shall be minimum 5 and maximum 10.
[25] Response Wait Time
All Modes
This value determines how long the Skyroute CL3050 will wait for a response
from Conect 24 before attempting to resend the same event.
Default - FA (250 seconds) range equals 01-FF Hex seconds.
NOTE: For UL Installations this must be 90 seconds (5A).