10 Test procedure  
 
Walk Test 
IMPORTANT NOTE: Once installed, the unit should be thoroughly tested to verify proper 
operation and coverage. After installation, the unit should be tested annually by the installer. The 
end user should be instructed on how to perform a weekly walk test. 
 
 
Ensure that the detector has completed the 2 minute warm up period before walk testing 
Make sure that the protected area is cleared of all people. 
Create motion in the entire area where coverage is desired by walking perpendicular to the 
detection pattern. 
Listen to ALARM sound whenever motion is detected (the red LED also turns ON whenever 
motion is detected).  
Allow 5 sec. between each test for the detector to stabilize. 
Walk across the entire area where coverage is desired. Should the coverage be incomplete, 
readjust coverage range or relocate the detector.  
Once coverage is as desired, the buzzer and LED should be disabled.