Digital Security Controls Ltd. 09LC171 User Manual

Page of 17
 
7 Terminal 
Block 
Connections 
 
Terminal 1 - Marked “-” (GND) - Connect to the ground of the Control Panel. 
Terminal 2 - Marked “+” (+12V) - Connect to a positive Voltage of 9.6 -16Vdc source 
(usually from the Control Panel) 
Terminals 3 & 4 - Marked “TAMP” - If a Tamper function is required connect these 
Terminals to a normally closed 24-Hour Tamper Zone on the Control Panel.  
If the top cover of the detector is opened or the detector is detached from installation wall, an 
immediate alarm signal will be sent to the Control Panel. 
Terminal 5 - Marked “EOL” - End of line – optional terminal for end of line resistors 
connections.  
Terminals 6, 7 & 8 - Marked “NC / C / NO” - These are the output relay contacts of the 
detector. Connect to a zone input on the control unit. When an intruder is detected, alarm 
relays (N.C. and N.O.)  will switch for 1.8 sec. 
 
7.1 Wire 
Size 
Requirements 
Use #22 AWG or larger wires. Use the following table to determine required wire gauge and 
length. 
Wire Length [m]    
205 
310 
510 
870 
Wire Length [ft.]    
800 
1200 
2000 
3400 
Wire Gauge [#]      
22 
20 
18 
16