Digital Security Controls Ltd. 17LE4000 User Manual

Page of 29
3
Safety Information
IMPORTANT
The equipment is fixed, wall-mounted and shall be installed in the position specified in these instructions. The equipment enclosure
must be fully assembled and closed, with all the necessary screws/tabs and secured to a wall before operation. Internal wiring must be
routed in a manner that prevents:
- Excessive strain on wire and on terminal connections
- Loosening of terminal; connections
- Damage of conductor insulation
WARNING:
 Never install this equipment during a lightning storm!
Instruct
 the end-user to:
-
 Not attempt to service this product. Opening or removing covers may expose the user to dangerous voltages or other risks. Any ser-
vicing
 shall be referred to trained service persons only.
-
 Use authorized accessories only with this equipment.
Do
 not dispose of the battery in fire or water. Disposing of the battery in a fire will cause rupture and explosion.
Do
 not dispose of the waste battery as unsorted municipal waste. Consult your local regulations and /or laws regarding recycling with 
regard
 to this lead-acid battery. Doing so will help protect the environment. Some of the materials that are found within the battery 
could
 become toxic if not disposed of properly and may affect the environment.
This
 equipment, LE4000, is fixed and shall be installed by Service Persons only (Service Person is defined as a person having the 
appropriate
 technical training and experience necessary to be aware of hazards to which that person may be exposed in performing a 
task,
 and of measures available to minimize the risks to that person or other persons). It shall be installed and used within an envir-
onment
 that provides the pollution degree max 2, over voltages category II, in non-hazardous, indoor locations only. This manual 
shall
 be used with the Installation Manual of the relevant alarm control panel. All instructions specified within that manual must be 
observed.
Approvals
 Information
For
 UL Residential Fire and Burglary installations, the LE4000 is listed as a sole means of communication or as a back up when used 
in
 conjunction with a POTS line (dialer). For UL Residential Fire installations, the LE4000 must be connected to a UL-listed power 
supply
 with a minimum of 24 hours standby power or powered using the ADP1310(W)-NAU and a 2200mAh battery.
For
 UL Commercial Burglary installations, the LE4000 is listed as a sole means of communication (supervision window of 200s 
required
 at monitoring station) or as a back-up when used in conjunction with a POTS line (dialer).
The
 LE4000 shall be powered from any compatible listed control unit or compatible listed power supply that complies with the ratings 
specified
 on page 1. The power supply shall be listed for burglary applications and provide a minimum of 4 hours standby power cap-
abilities.
 An example of a suitable listed compatible control unit is the DSC Model PC1864 with an AUX output rated 11.1 - 
12.6Vdc.
 An example of a suitable Listed power supply is DSC Model PC5204 with an AUX output rated 11.6 - 12.6Vdc.
For
 ULC Commercial Burglary installations the LE4000 is listed as a passive communication system with communication line secur-
ity
 level P1 when used as single communication path or P2 when used as a back up in conjunction with a POTS line (dialer). The 
LE4000
 is also listed for Active line security levels A1-A4 (90 seconds heartbeat enabled and supervision window of 180s required 
at
 monitoring station receiver). For ULC Commercial Burg installations, the LE4000 must be connected to a ULC-listed power 
supply
 with a minimum of 24 hours standby power or powered using the ADP1310(W)-NA and a 2200mAh battery. The LE4000 
can be used in commercial burglary applications up to Security Level IV.
For
 ULC Residential Fire and Burglary installations the LE4000 is listed as a sole means of communication or as a back up when 
used
 in conjunction with a POTS line (dialer). For ULC Residential Fire installations, the LE4000 must be connected to a ULC-
listed
 power supply with a minimum of 24 hours standby power or powered using the ADP1310(W)-NA and a 2200mAh battery.