EFAULTS
[999] Software Default
Default (99);
The Software default allows the installer to refresh the unit after changes and also return the
Communicator to the default state.
00:  Default Module. All programming Sections in module revert to factory settings. This will
erase all existing programming of the unit.
55:  Reset. The Communicator is reset. This option is equivalent to power cycling the
Communicator.
C
OMMUNICATOR
 T
ROUBLESHOOTING
[984] Communicator Status
The communicator status sections are intended to provide the installer with real-time status of 
the communicator’s functionality, operational readiness, failures, and potential malfunctions 
that may affect flawless operation of the communicator and its primary function of sending sig-
nal to the central station in case the monitored event occurs.
The communicator status is displayed in the form of a 6-digit CODE (6 hexadecimal numbers) 
as in the following pattern: 00000F. The range of the code is from: 00000F – 2220CF. Not all 
numbers in this range are assigned a status code (Some numbers are skipped, i.e. not assigned 
the code).
Each digit represents a status or trouble indicator (or assigned function when no trouble is pres-
ent) as described below:
1. Digit 1 - Signal Indicator 1, displays the presence/strength of signal 1.
2. Digit 2 - Signal Indicator 2, displays the presence/strength of signal 2.
3. Digit 3 - Network Indicator, displays the presence (operational status) of network.
4. Digit 4 & 5 – TROUBLE INDICATOR displays the type of problem/malfunction on
communicator or modules associated with and connected to communicator.
5. Digit 6 – Reserved for future use.
For example, status code 11002F – when interpreted means: “Signal Indicator 1 OK, Signal 
indicator 2 OK, there is no network trouble, and there is trouble in the communicator, Panel 
supervision trouble.” For details see the table below:
Table 16: Communicator Status and Trouble Coding in Hexadecimal Numbers
Digit 1
Digit 2
Digit 3
Digit 4 & 5
Digit 6
Signal indicator 1
Signal indicator 2
Network indica-
tor
TROUBLE INDICATOR
Future 
use
0
Off
0
Off
0
Off
00
Off  (No trouble)
F
1
On
1
On
1
On
01
Future use
F
2
Flashing
2
Flashing
2
Flashing
02
Panel supervision trouble
F
03
Future use
F
04
Lockout trouble
F
05
3G/Cellular trouble
F
06
Ethernet Trouble
F
07
Receiver Not Available
F
08
Receiver Supervision trouble
F
09
FTC Trouble
F
0A
C24 Configuration SMS Failure
F
0B
Future use
F
0C
Module configuration Trouble
F