Digital Monitoring Products Inc PC0126P User Manual

Page of 10
9000 Series Installation Guide 
Digital Monitoring Products
3
Battery Replacement
1.  Disconnect the battery lead connector from the 
keypad J3 battery header.
2.  Remove the battery strap from the standby battery.
3.  Remove and properly dispose of the used battery. 
Caution: Risk of fire, explosion, and burns.  Do not  
disassemble, heat above 212°F (100°C), or incinerate.   
Properly dispose of used batteries. 
4.  Place the new battery on the keypad PCB and replace 
the battery strap.
5.  Observe polarity and connect the battery lead 
connector to the keypad J3 battery header. 
Installing Keypad PCB
1.  Set the keypad PCB into the bottom snaps
2.  Line  up  the  PCB  alignment  post  with  the  hole  in  the 
keypad PCB.
3.  Press the PCB into the top PCB snaps to secure in place.  
4.  Replace the base.
Battery Supervision
The panel tests the battery once every hour when DC power is present.  This test occurs 15 minutes past each hour and 
lasts for five seconds.  A load is placed on the battery and if the battery voltage is low, a low battery is detected.  If DC 
power has failed, a low battery is detected any time the battery voltage falls below
 
3.7V.
Card Reader
When a proximity credential is presented to the Model 9063 internal reader, a beep tone is heard and the Power and Armed 
LEDs blink.  This provides both an audible and visual acknowledgement of the credential read. 
Panic Key Options
2-Button Panic Keys
All keypads offer Panic key function that allows users to send Panic, Emergency, or Fire reports to the central station.  
Enable the Panic key function in the keypad user menu.  See Keypad Programming Instructions later in this document.  
Install the supplied icon labels below the top row of Select keys as shown in Figure 4.   
The user must press and hold the two Select keys for two seconds until a beep from the keypad is heard.  At the beep, the 
panel sends the following zone alarm reports to the central station: 
  Panic (left two Select keys)—Zone 19 + Device Address 
Emergency—non-medical (center two Select keys)—Zone 29 + Device Address 
Fire (right two Select keys)—Zone 39 + Device Address
Internal Speaker Operation
All keypads emit standard tones for key presses, entry delay, and system alerts.  The speaker also provides distinct 
burglary, fire, zone monitor, and prewarn cadences.  The keypads provide an alternate prewarn with alarm cadence that 
occurs when the status list displays a zone alarm.
Backlighting
Both the logo and keyboard light when a key is pressed or the speaker sounds.  
During an alarm condition, all lighted areas turn Red.  When all alarm conditions are cleared from the display, the Red 
display turns off and the lighted areas return to the user-selected brightness.  
Backlit Keyboard and Logo
The backlit keyboard and logo indicate the power and armed status of the panel.  Depending on the status, the LED 
displays in Red or Green as listed in the table.
Color and Activity
Operation
Green Steady
Panel Disarmed, AC Power OK, Battery OK
Green Blinking
Panel Disarmed, AC Power OK, Battery Fault
No Light
Panel Disarmed, AC Power Fault, Battery OK
Red Steady
Panel Armed, AC Power OK, Battery OK
Red/Green Alternate
Panel Armed, AC Power OK, Battery Fault
Red Blinking
Panel Armed, AC Power Fault, Battery OK
Standby battery 
connector
Standby 
battery 
strap
Figure 5: Battery Replacement