Digital Monitoring Products Inc PC0128 User Manual

Page of 31
XT30/XT50 Installation Guide 
Digital Monitoring Products
5
InstallatIon
3.4  XT30/XT50 Wiring Diagram
16 to 18 
gauge wire
Maximum AC 
Wire distance –
16 gauge wire: 70 feet
18 gauge wire: 40 feet
RED
BLACK
Earth Ground 
s
s
s
s
USE MARKING
Commercial  Central Station; Household Fire and 
Burglar Warning System Control Unit (DACT, 
PSDN: IP or Cellular)
NFPA 72
This equipment should be installed in accordance with Chapter 11 
of the National Fire Alarm Code, ANSI/NFPA 72-2002, (National 
Fire Protection Association, Batterymarch Park, Quincy, MA 
02269). Printed information describing proper installation,
operation, testing, maintenance, evacuation planning, and repair
service is to be provided with this equipment. Warning: Owner’s
instruction notice, not to be removed by anyone except occupant.
HOUSEHOLD FIRE WIRING
Recognized limited energy cable must be 
used for connection of all initiating,
indicating, and supplementary devices.
POWER LIMITED
All circuits on the Model XT30/XT50 comply 
with the requirements for inherent power 
limitation and are Class 2.
TYPES OF SERVICE
Suitable for DACT Central Station. 
Suitable for Household Fire and 
Household Burglary. Test weekly.
SIA CP-01-2010 minimum system is
XT30 or XT50, local Bell, and off
premise DACT communication to an 
SCS-1R receiver plus ANSI/SIA 
CP-01-2010 classified compatible DMP 
keypads as indicated in the installation 
guide.
J3
Phone Line
Outputs
J11
1
2
3
4
J1
Ethernet
J16
Reset
J20
Wireless 
Antenna
connection
J7 RJ 
Supervision
XT30/XT50
Command Processor™ Panel
RED
PROG
J8
Programmer Header J8 
Use DMP Model 330 Harness
Terminals 5-20 are Power Limited.
Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
Plug into 
120 VAC 
60 Hz 
outlet not 
controlled 
by switch.
Zone 10 compatibility
identifier: A
Maximum operating
range:
8.8 VDC - 14.2 VDC.
DMP Transformers
Model 321 – 16.5 VAC 40 VA
Class 2 plug-in.
Model 320 – 16.5 VAC 40 VA
Class 2 wire-in.
Verification
Zone
10
Control Unit
Delay
13.6 sec.
Smoke
Model
______
Detector
Delay
____sec.
Heat detectors, manual pull stations, or any 
other shorting device. Unlimited number of 
units.
1K Ohm EOL
on each zone
3.3K Ohm EOL
Switched
Voltage
Output
Zone 10
Keypad
Bus
Smoke
Zones 1 to 9
Bell
Secondary Power Supply
1.2 Amps maximum charging current.  Use only 
12 VDC rechargeable batteries.  Replace every 3 
to 5 years.
Minimum voltage on 
Auxiliary output to 
process Sensor trips 
is 10.4 VDC.
For Wireless Devices, Control Unit delay is 0 (zero).
Bell — 10.2 - 13.9 VDC
Total current: 1.5 Amps max. 
w/ 40 VA.
AUX (RED) — Up to 500mA 
auxiliary current at 10.2 VDC - 
13.9 VDC from Terminal 7.
Up to 325mA auxiliary current 
at 10.2 VDC - 13.9 VDC from 
Termical 7 when using (2) 
Model 364 1.3Ah Batteries.
Smoke Output: — 100mA at 
10.2 - 13.9
 VDC Terminal 11.
Smoke
Detector
1k Ohm
s
s
To Keypad
or Zone
Expander
For listed applications the maximum current from a combination of bell
output, auxillary output, and smoke output is 1.6 amps.
65555
263
Module
AC Wiring must be in conduit and exit 
out the left side of the enclosure.  
Wiring on terminals 5 through 26 
must exit right and maintain a 1/4" 
separation from the AC and battery 
positive wiring.  
Figure 1: System Wiring Diagram