Digital Monitoring Products Inc PC0194 User Manual
Choose one of the AC-powered interconneted smoke detectors
onto which you will add the 1166. The 1166 will use this smoke
detector for communication. The smoke detector must be within
range of a DMP wireless receiver or panel to ensure proper
communication.
1. Disconnect power from the smoke detector system before
beginning the installation.
2. Remove the chosen smoke detector from its mounting base
by twisting it counter clockwise or clockwise (depending on
the brand).
3. Unplug the pigtail connector and detach the smoke
detector.
4. Remove the screws from the mounting bracket to detach it
from the electric junction box.
5. Insert the pigtail wire and wire taps through the center
opening in the 1166.
6. Place the 1166 where the mounting base was on the ceiling
or wall.
7. Place the mounting base over the 1166 and line up the screw
openings.
8. Use the mounting screws included with the 1166 to attach
the mounting base and 1166 to the electric junction box.
1166 WIRELESS SMOKE RING
Installation Guide
1
The 1166 Wireless Smoke Ring can
be installed with any traditional
AC-powered interconnected smoke
detector system.
Traditional smoke detectors only
provide an audible alert in the event
of a fire. The 1166 monitors the
smoke detector system and sends a
message to the alarm panel when a
smoke detector is triggered.
Only one 1166 is required per smoke
detector system.
Compatibility
All DMP 1100 Series Wireless Receivers
and burglary panels. See the last page
for compatibility details.
Smoke Detectors
BRK Brands Model 7010B
Firex Kidde Model i4618
First Alert BRK Model 9120B
Kidde Model i12040
USI Electric Model 5304
What is Included?
One 1166 Wireless Smoke Ring
One 3V lithium CR2477 battery
Mounting screws
Figure 1: 1166 Wireless
Smoke Ring
DESCRIPTION
PROGRAM THE PANEL
Begin by programming the 1166 Wireless Smoke Ring into the
panel. Refer to the panel programming guide as needed.
1. In
ZONE INFORMATION, enter the ZONE number and press
CMD.
2. Enter the
ZONE NAME and press CMD.
3. Select
FI (Fire) as the Zone Type and press CMD.
4. At the
NEXT ZONE prompt, select NO. If you see the
WIRELESS ZONE prompt, select YES.
5. Enter the eight-digit
SERIAL NUMBER and press CMD.
6. Enter the
SUPRVSN TIME and press CMD.
7. At the
NEXT ZONE prompt, select NO.
SELECT A SMOKE DETECTOR
2