 1166 INSTALLATION GUIDE     |     DIGITAL MONITORING PRODUCTS         
                       3
TEST THE 1166
After you have installed the 1166, perform one of the following tests to ensure that the 1166 is successfully sending messages 
to the panel. These tests can be performed on any of the system’s smoke detectors. 
Press the Test Button
Press the Test button on one of the smoke detectors where the 1166 is located. If the 1166 is communicating properly, an alarm 
message on the 1166’s zone will be transmitted to the panel.
Smoke Testing
1. 
Use canned smoke or a smoldering punk to direct smoke into the openings of one of the smoke detectors for 20 
seconds or until it goes into alarm.  
2.  The detector’s red LED should stay on and the panel should recognize an alarm. Use the system reset switch to reset 
the detector. 
Caution: Remember to extinguish the smoke source after testing. 