Choose one of the AC-powered interconneted smoke detectors 
onto which you will add the 1166. The 1166 will use this smoke 
detector for communication. The smoke detector must be within 
range of a DMP wireless receiver or panel to ensure proper 
communication.
1.  Disconnect power from the smoke detector system before 
beginning the installation.
2.  Remove the chosen smoke detector from its mounting base 
by twisting it counter clockwise or clockwise (depending on 
the brand).
3.  Unplug the pigtail connector and detach the smoke 
detector.
4.  Remove the screws from the mounting bracket to detach it 
from the electric junction box.
5.  Insert the pigtail wire and wire taps through the center 
opening in the 1166.
6.  Place the 1166 where the mounting base was on the ceiling 
or wall.
7.  Place the mounting base over the 1166 and line up the screw 
openings.
8.  Use the mounting screws included with the 1166 to attach 
the mounting base and 1166 to the electric junction box.
1166 WIRELESS SMOKE RING
Installation Guide
1
The 1166 Wireless Smoke Ring can 
be installed with any traditional 
AC-powered interconnected smoke 
detector system. 
Traditional smoke detectors only 
provide an audible alert in the event 
of a fire. The 1166 monitors the 
smoke detector system and sends a 
message to the alarm panel when a 
smoke detector is triggered.
Only one 1166 is required per smoke 
detector system.
Compatibility
All DMP 1100 Series Wireless Receivers 
and burglary panels. See the last page 
for compatibility details.
Smoke Detectors
 
ƒ
BRK Brands Model 7010B
 
ƒ
Firex Kidde Model i4618
 
ƒ
First Alert BRK Model 9120B
 
ƒ
Kidde Model i12040
 
ƒ
USI Electric Model 5304
What is Included?
 
ƒ
One 1166 Wireless Smoke Ring
 
ƒ
One 3V lithium CR2477 battery
 
ƒ
Mounting screws
Figure 1: 1166 Wireless  
Smoke Ring
DESCRIPTION
PROGRAM THE PANEL
Begin by programming the 1166 Wireless Smoke Ring into the 
panel. Refer to the panel programming guide as needed.
1.  In 
ZONE INFORMATION, enter the ZONE number and press 
CMD. 
2.  Enter the 
ZONE NAME and press CMD.
3.  Select 
FI (Fire) as the Zone Type and press CMD. 
4.  At the 
NEXT  ZONE prompt, select NO. If you see the 
WIRELESS ZONE prompt, select YES.
5.  Enter the eight-digit 
SERIAL NUMBER and press CMD.
6.  Enter the 
SUPRVSN TIME and press CMD. 
7.  At the 
NEXT  ZONE prompt, select NO.